Field Supplied Refrigerant Piping Type ACR copper is the only approved refrigerant pipe material for use with LG Multi F air conditioning products. ACR rated tubing is the only type that ships with yellow caps. Approved tubing for use with Multi F products will be marked “R410 RATED” along the length of the tube.
Field-Provided Isolation Ball Valves LG recommends installing field-supplied ball valves with Schrader ports at each indoor unit. Full-port isolation ball valves with Schrader ports (positioned between valve and indoor unit) rated for use with R410A refrigerant should be used on both the liquid and vapor lines.
Page 23
Multi F MAX Y-Branch Kit PMBL5620 The LG supplied Y-Branch Kit PMBL5620 MUST be used when two branch distribution units are connected to one Multi F MAX system. Field-supplied fittings are not permitted. Each Y-Branch kit comes with two (2) Y-branches (one for the liquid line and one for the vapor line) and insulation covers.
Page 24
Tube wall thickness should meet local code requirements and be approved for an operating pressure of 551 psi. If local code does not specify wall thickness, LG suggests using tube thickness per table below. When bending tubing, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed pipe;...
Page 36
Ensure all refrigerant piping is insulated. Any exposed piping will cause burns if touched. Wrap all refrigerant and condensate piping including field-provided isolation ball valves and flexible pipe connection kits provided by LG. All pipes must be insulated and each pipe must be separately wrapped. Any exposed piping may generate condensate; sufficiently insulate all cold surfaces to prevent moisture forming.
(55) inches above the finished floor. • It may be necessary to use a handy box that is sized in metric units, depending on the controller model. Check with your LG representative to verify which size of handy box is needed for the zone controller in question.
Page 53
Power wiring to the Single Zone outdoor unit was installed per all local electrical code requirements. Power wiring to the indoor unit was installed per all local electrical code requirements. LG-supplied cable was used between the indoor unit and its zone controller. No cables were spliced and no wire caps are present.
Page 56
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics LG Customer Information Center, Commercial Products Commercial Air Conditioning Division 1-888-865-3026 USA 11405 Old Roswell Road Follow the prompts for commercial A/C products and parts. Alpharetta, Georgia 30009 IM_Multi_F_ArtCoolMirrorWallMount_5_15 www.lghvac.com Original Issue...