Cooling capacity.Designed for Low-noise operation,it ensures a pleasant air conditioned environment. LG O ers various types of units to its customers to suit for the best application and requirement.The following are the important categories o ered by LG : 1) Art Cool Units : A new concept of cooling introduced by LG in the eld of Air Conditioning.
Models line up 6RMI0-04C 1.2 Outdoor Unit ASUW093B1Y9(LSU091HSV2) ASUW123B1Y9(LSU121HSV2) Heat pump ASUW093BRM9(LAU090HSV2) ASUW123BRM9(LAU120HSV2) ASUW093F2B2(LAU090HVP) ASUW123F2B2(LAU120HVP) Total capacity index of connectable 2.64 3.28 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis Heat pump ASUW093MMM9(LSU090HYV) ASUW123MMM9(LSU120HYV) Total capacity index of connectable 2.64 3.51 indoor units...
Page 8
6RMI0-04C Models line up ASUW183C2Y9(LSU181HSV2) ASUW243DGY9(LSU240HSV2) Heat pump ASUW183CRM9(LAU180HSV2) ASUW243CRM9(LAU240HSV2) Total capacity index of connectable 5.33 6.45 indoor units kBtu/h Power supply 1Φ / 208~230V / 60Hz Chassis UE1+ ASUW303DGY9(LSU307HV2) ASUW363DGY9(LSU360HV2) Heat pump Total capacity index of connectable 8.79 9.67 indoor units kBtu/h Power supply...
Nomenclature 6RMI0-04C 2. Nomenclature • Model Number Serial Number Function H : Plasma + (A/chageove) + A/Clean + 4Way + Low A U : Plasma + Allergy Filter + 4Way Z : Basic + (A/clean) + 4Way + Low A Look/Color CHASSIS LOOK...
Page 13
6RMI0-04C Art Cool Premier Inverter Sales Model LSN090HYV/LSU090HYV LSN120HYV/LSU120HYV Models Unit AS-W093MMM9 AS-W123MMM9 Cooling Capacity 0.30~2.63~3.80 0.30~3.51~4.04 Btu/h. 1,023~9,000~12,966 1,023~12,000~13,785 Heating Capacity 0.30~3.22~6.50 0.30~3.98~6.50 Btu/h. 1,023~11,000~20,472 1,023~13,600~22,178 Power Input Cooling/Heating 550 / 740 850 / 960 Running Current Cooling/Heating 2.5/3.4 3.8 / 4.3...
Page 14
6RMI0-05A Speci cations Art Cool Gallery Inverter Cooling Capacity . h / Heating Capacity . h / n i l n i l n i l Cooling COP SEER HSPF Ø Air Flow Rate . h / ± ) Sound Level ±...
6RMI0-04C Refrigerant cycle diagram 6. Refrigerant cycle diagram Model No : AS-W093MMM9(LSN090HYV/LSU090HYV), AS-W123MMM9(LSN120HYV/LSU120HYV) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating Description PCB Connector LOC.
Page 31
Refrigerant cycle diagram 6RMI0-04C Models : AS-W093BRM9(LAN090HSV2/LAU090HSV2), AS-W123BRM9(LAN120HSV2/LAU120HSV2) AS-W093B1Y9(LSN091HSV2/LSU091HSV2), AS-W123B1Y9(LSN121HSV2/LSU121HSV2) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for sunction air temperature CN-TH1(Indoor) Water Level Sensor (Option) CN-TH2(Indoor)
Page 32
6RMI0-04C Refrigerant cycle diagram Models : AS-W183CRM9(LAN180HSV2/LAU180HSV2), AS-W243CRM9(LAN240HSV2/LAU240HSV2), AS-W183C2Y9(LSN181HSV2/LSU181HSV2) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature Thermistor for evaporator outlet temperature + Water level sensor...
Page 33
Refrigerant cycle diagram 6RMI0-04C Models : AS-W243DGY9(LSN240HSV2/LSU240HSV2), AS-W303DGY9(LSN307HV2/LSU307HV2) AS-W363DGY9(LSN360HV2/LSU360HV2) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating LOC. Description PCB Connector Thermistor for suction air temperature CN-TH1(Indoor) Thermistor for evaporator inlet temperature Thermistor for evaporator outlet temperature...
Page 34
6RMI0-04C Refrigerant cycle diagram Models : AS-W093F2B2(LAN090HVP/LAU090HVP), AS-W123F2B2(LAN120HVP/LAU120HVP) Indoor Unit Outdoor Unit Liquid Side 2-Way Valve Heat Heat Exchanger Exchanger (Evaporator) (Condenser) Gas Side Reversing Valve Accumulator 3-Way Valve Cooling Compressor Heating Description PCB Connector Thermistor for indoor air temperature CN_TH1(INDOOR) Water level sensor (Option) CN_TH2(INDOOR)
Electric characteristics 6RMI0-04C 9. Electric characteristics Unit Power Compressor Model Type Voltage Voltage range MCA MOP MSC ASUW093F2B2(LAU090HVP) 0.08 0.25 ASUW123F2B2(LAU120HVP) 0.08 0.25 ASUW093MMM9(LSU090HYV) 0.12 1.04 ASUW123MMM9(LSU120HYV) 0.12 1.04 ASUW093BRM9(LAU090HSV2) 0.08 0.45 ASUW123BRM9(LAU120HSV2) 0.08 0.45 ASUW183CRM9(LAU180HSV2) 14.6 0.12 0.75 MIN : 187 Inverter 60 208~230 MAX : 253...
6RMI0-04C Operation range 10. Operation range Cooling Heating 48(118°F) Outdoor Unit Continuous [°C DB] 24(75°F) operation Continuous Outdoor Unit operation [°C DB] -10(14°F) -10(14°F) 18(64°F) 32(90°F) 16(61°F) 30(86°F) Indoor Unit [°C DB] Indoor Unit [°C DB] Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease.
Page 51
Operation range 6RMI0-04C Cooling Heating 48(118°F) Outdoor Unit [°C DB] 24(75°F) Continuous operation Outdoor Continuous Unit operation [°C DB] -10(14°F) -15(5°F) 18(64°F) 32(90°F) 16(61°F) 30(86°F) Indoor Unit [°C DB] Indoor Unit [°C DB] Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease.
6RMI0-05A Air ow and temperature distributions(reference data) 11. Air ow and temperature distributions(reference data) 2.64 kW (9kBtu/h) – LAN090HSV2 / LSN091HSV2 Cooling Heating Discharge angle:45° Discharge angle:50° Air velocity [ft/s] Air velocity [ft/s] 8.9ft 8.9ft 6.6ft 6.6ft 4.0ft 4.0ft 16.4ft 13.1ft 9.8ft 6.6ft...
Page 53
o l f t s i b i r i t u r e f ) a t - 0 I 5.33 kW (18kBtu/h) – LAN180HSV2 / LSN181HSV2 Cooling Heating Discharge angle:45° Discharge angle:50° Air velocity [ft/s] Air velocity [ft/s] 8.9ft 8.9ft 6.6ft...
Page 54
6RMI0-05A Air ow and temperature distributions(reference data) 6.45 kW (24kBtu/h)/8.79 kW (30kBtu/h) – LSN240HSV2/LSN307HV2 Cooling Heating Discharge angle:49° Discharge angle:65° Air velocity [ft/s] Air velocity [ft/s] 8.9ft 8.9ft 6.6ft 6.6ft 11.5 13.1 4.0ft 4.0ft 13.1 14.8 9.8 11.5 26.2ft 23ft 19.7ft 16.4ft 13.1ft...
Page 55
) a t - 0 I Art Cool Premier Inverter 2.64 kW (9kBtu/h) - LSN090HYV Cooling Heating Discharge angle:45° Discharge angle:50° Air Velocity [ft/s] Air Velocity [ft/s] 8.9ft...
Page 56
6RMI0-05A Air ow and temperature distributions(reference data) Art Cool Gallery 2.64kW(9kBtu/h) – LAN090HVP Cooling Heating Discharge angle:52° Discharge angle:52° Based on maximum air ow. Art Cool Gallery 3.28 kW(12kBtu/h) –LAN120HVP Cooling Heating Discharge angle:45° Discharge angle:50° Inverter Single Inverter Single...
6RMI0-04C Sound level 12.2 Outdoor Units Overall Notes: - Sound measured at 1m(3.28 ft) away from the center of the unit. - Data is valid at free eld condition. Center of Center of - Data is valid at nominal operation condition. Outdoor Unit Outdoor Unit - Reference accoustic pressure 0dB=20Pa.
Remote controller 6RMI0-04C 13. Remote controller Wireless Remote Controller Control Display Description panel screen Plasma button*: Purifies the air by removing particles that enter the indoor unit. Display Sleep mode auto button*: Sets the sleep screen mode auto operation. Temperature adjustment buttons: Adjusts the room temperature when cooling and heating.
6RMI0-04C Remote controller 1. START/STOP BUTTON The controls will look like the following. Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Signal transmitter Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4.
Installation 6RMI0-04C 14. Installation Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) • Apply after carrying out a drainage test. •...
6RMI0-04C Installation Select the best Location Indoor unit 1. There should not be any heat or steam near the unit. minimum distance minimum distance to the side : 102(4) 2. Select a place where there are no obstacles around to the ceiling : 203(8) of the unit.
Page 64
Installation 6RMI0-04C Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with Installation Plate type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Page 65
6RMI0-04C Installation Type 3 780(30 11/16) 858(33 13/16) [Unit : mm(inch)] • Applied Model : LS240HSV2/LS307HV2/LS360HV2 Type 4 Place a level on raised tab Unit Outline 434(17) 439(17 5/16) Ø65(2 9/16) Ø65(2 9/16) Installation Plate 170(6 11/16) 123(4 13/16) 175(6 29/32) 217(8 17/32) •...
Installation 6RMI0-04C Flaring Work One cause of gas leakage is improper workmanship in aring . Carry out correct aring work in the following procedure. Cut the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally.
Page 67
6RMI0-04C Installation Connecting the Piping Inverter Single...
Installation 6RMI0-04C Installation Information. For right piping. Follow the instruction below. Good case • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. Bad case • Following bending case from right to left directly may cause damage to the tubing. Inverter Single...
6RMI0-04C Installation Installation of Indoor Unit 1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right Installation plate...
Installation 6RMI0-04C If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating (condensation) will not damage furniture or oors. Be sure to install in the sequence of Connecting cable (Conduit), Drain hose and Connecting pipe as the picture below describes.
Page 71
6RMI0-04C Installation Wrap the insulation material around the connecting Insulation material portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap. Cutting Line 2.
Page 72
Installation 6RMI0-04C Outdoor unit 1. Remove the tubing cover from the unit by loosening the screw. Tubing cover 2. Align the center of the pipings and su ciently tighten the are nut by hand. 3. Finally, tighten the are nut with torque wrench until the wrench clicks.
Page 73
6RMI0-04C Installation Connecting the Cables Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
Page 74
Installation 6RMI0-04C Outdoor 1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control Terminal block board individually as the following. Over 5mm 2. Secure the cable onto the control board with the (0.2") holder (clamper).
Page 76
Installation 6RMI0-04C How to connect wiring to the Power supply cable terminals Strand wire For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the strand Round terminal wiring about 10mm(3/8in). (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate.
6RMI0-04C Installation Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water ows through the drain Connecting area drain hose hose of the indoor unit without any leakage and goes out the drain exit. Leakage checking Drain pan...
Page 78
Installation 6RMI0-04C Forming the Piping In cases where the outdoor unit is Seal the small installed below the indoor unit openings around perform the following. pipings with a gum type sealants. 1. Tape the piping, drain hose and connecting cable Connecting cable from down to up.
6RMI0-04C Installation Air Purging The air and moisture remaining in the refrigerant system have undesirable e ects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) e ciency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5.
Installation 6RMI0-04C Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. Liquid side 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit Gas side connections by a soft brush to check for leakage of the connecting points of the piping.
Page 81
6RMI0-04C Installation Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction.
Installation 6RMI0-04C Settlement of outdoor unit Bolt 1. Fix the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount. 2. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the in uence of wind and earthquake.
Page 83
3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water...
Page 84
20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com All rights reserved The air conditioners manufactured by LG have received ISO9001 certificate for Printed in Korea January/2013 quality assurance and ISO14001 certificate for environmental management system. The specifications, designs, and information in this brochure are subject to change without notice.