Job Name/Location:
Date:
PO No.:
Architect:
Engr:
Rep:
(Company)
LA120HYV
Art Cool™ Premier Single Zone Inverter
Outdoor Unit (ODU) - LAU120HYV
Performance:
Cooling:
Capacity (Btu/h)
SEER
EER
SEER - Seasonal Energy Efficiency Ratio EER - Energy Efficiency Ratio
Heating:
Capacity (Btu/h)
HSPF
HSPF - Heating Seasonal Performance Factor
Cooling Nominal Test Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
Electrical:
Power Supply (V¹/Hz/Ø)
Outdoor Unit:
MOP (A)
MCA (A)
Cooling Rated Amps (A)
Heating Rated Amps (A)
Compressor (A)
Fan Motor (A)
MOP - Maximum Overcurrent Protection MCA - Minimum Circuit Ampacity
Total Power Input:
Cooling Power Input (kW)
Heating Power Input (kW)
Piping:
Liquid Line (in, OD)
Vapor Line (in, OD)
Additional Refrigerant (oz/ft)
Max Pipe Length (ft)²
Piping Length (no add'l refrigerant, ft)
Max Elevation (ft)
Controls Features:
•Condensate sensor 
•24-Hour on/off  mer
connection
•4-Way auto swing
•Defrost control
•Auto changeover
•Dehumidifying mode
•Auto restart
•Hot start
•Built-in low ambient 
•Jet cool/Jet heat
operation to 14°F
•Self cleaning indoor coil
•Chaos wind
Optional Accessories (sold separately):
LG Programmable Thermostat - PREMTB10U
Dry Contact for third party thermostat - PQDSBNGCM1
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com
For:
GC:
Mech:
(Project Manager)
Indoor Unit (IDU) - LAN120HYV
12,000
25.5
14.1
13,600
11.5
Heating Nominal Test Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
208-230/60/1
11.2
8.70
8.70
8.3
0.40
0.85
0.86
1/4
3/8
0.22
65.6
41.0
32.8
•Self diagnosis
•Sleep mode
•So  dry opera on
•Ultra quiet opera on
•Cooling only switch
File
Resubmit
Approval
Other
Operating Range:
Outdoor Unit:
Cooling (°F DB)
Heating (°F WB)
Indoor Unit:
Cooling (°F WB)
Heating (°F DB)
Unit Data:
Refrigerant Type
Refrigerant Control
Refrigerant Charge (lbs)
ODU Sound Pressure (Max) ±3 dB(A)³
IDU Sound Pressure (H/M/L/Sleep) ±3 dB(A)³
ODU Net Unit Weight (lbs)
ODU Shipping Weight (lbs)
IDU Net Unit Weight (lbs)
15
IDU Shipping Weight (lbs)
Heat Exchanger Coating
Fan:
ODU Type
IDU Type
Fan Speeds (Fan/Cooling/Heating)
Quantity (ODU + IDU)
Motor/Drive
ODU Max Air Flow Rate (CFM)
IDU Air Flow H/M/L (CFM)
Dehumidification (pts/hr)
Notes:
1.Acceptable opera ng voltage: 187V - 253V.
2.Piping lengths are equivalent.
3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4.All power/communica on cable to be minimum 18 AWG, 4-conductor, stranded, shielded 
and must comply with applicable local and national code.
5.See Engineering Manual for sensible and latent capaci es.
6.Power wiring cable size must comply with the applicable local and na onal code.
7.The indoor unit comes with a dry helium charge.
8.This data is rated 0   above sea level, with 24.6   of refrigerant line and a 0   level 
difference between outdoor and indoor units.  
9.Must follow installa on instruc ons in the applicable LG installa on manual.
Tag #:
Brushless Digitally Controlled/Direct
DFS-SB-AG-004-US 013J05
14-118
-13-75
64-90
60-86
R410A
EEV
2.54
45
42/36/25/17
73
78
25
29
GoldFin™
Propeller
Cross Flow
6/6/6
1 + 1
1,165
494/417/283
3.7
Page 1 of 3

Advertisement

loading

Summary of Contents for LG LA120HYV

  • Page 1 4.All power/communica on cable to be minimum 18 AWG, 4-conductor, stranded, shielded  and must comply with applicable local and national code. Max Pipe Length (ft)² 65.6 5.See Engineering Manual for sensible and latent capaci es. Piping Length (no add'l refrigerant, ft) 41.0 6.Power wiring cable size must comply with the applicable local and na onal code. 7.The indoor unit comes with a dry helium charge. Max Elevation (ft) 32.8 8.This data is rated 0   above sea level, with 24.6   of refrigerant line and a 0   level  difference between outdoor and indoor units.   Controls Features: 9.Must follow installa on instruc ons in the applicable LG installa on manual. •Condensate sensor  •Self diagnosis •24-Hour on/off  mer connection •Sleep mode •4-Way auto swing •Defrost control •So  dry opera on •Auto changeover •Dehumidifying mode •Ultra quiet opera on •Auto restart •Hot start •Cooling only switch...
  • Page 2 Job Name/Location: Outdoor Unit (ODU) - LAU120HYV Tag #: Date: Art Cool™ Premier Single Zone Inverter PO No.: For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com DFS-SB-AG-004-US 013J05 Page 2 of 3...
  • Page 3 Job Name/Location: Indoor Unit (IDU) ‐ LAN120HYV Tag #: Date: Art Cool™ Premier Single Zone Inverter PO No.: For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com DFS‐SB‐AG‐004‐US 013J05 Page 3 of 3...