instAllAtion And MAintenAnCe instruCtions
FCM-1-relA releasing Control Module
speCiFiCAtions
slC
Normal Operating Voltage:
Average Operating Current:
Maximum Activation Current:
external supply
Normal Operating Voltage:
Maximum Line Loss:
Minimum Operating Voltage to Activate Solenoid:
Standby Current:
Activation Current:
Maximum Activation Current:
solenoid
Supervisory Loop Voltage:
Supervisory Loop Current (Normal):
Maximum Activation Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
BeFore instAlling
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
generAl desCription
FCM-1-RELA Releasing Control Modules are intended for use in intelligent,
two-wire systems, where the individual address of each module is selected
using the built-in rotary switches. This module is used to switch an external
power supply, which can be a DC power supply to a solenoid. It also super-
vises the wiring to the connected load and reports the status to the panel as
NORMAL, OPEN, or SHORT CIRCUIT. The FCM-1-RELA has two pairs of
output termination points available for fault-tolerant wiring and a panel-con-
trolled LED indicator.
CoMpAtiBility requireMents
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panels only (list available from Notifier). In addition,
please refer to Notifier Device Compatibility document number 15378 for the
list of compatible solenoids.
Mounting
The FCM-1-RELA mounts directly to 4-inch square electrical boxes (see Fig-
ure 2). The box must have a minimum depth of 2
electrical boxes (SMB500) are available (for indoor dry applications only).
Figure 1A. Controls And
indiCAtors
15 to 32 VDC Nominal
700µA (LED flashing)
9.0 mA (red LED on)
24 VDC Nominal
2.3 VDC (total allowable loss from power supply to module and from module to solenoid)
18 VDC (at solenoid)
6.4 mA
10 mA
2 A
3.3 V
30 mA
2 A
32°F to 120°F (0°C to 49°C)
10% to 95% RH Non-condensing
4
1
/
˝ H × 4˝ W × 1
2
Wall cover plate (included); SMB500 Surface Mount Electrical Box (for indoor dry applications only)
1
/
inches. Surface mounted
8
Figure 1B.JuMper loCAtion:
J1
C1059-00
1
/
˝ D; (106 mm H × 108 mm W × 31 mm D)
4
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), as shown in Fig-
ure 2.
IMPORTANT: When using the FCM-1-RELA for Class B applications, remove
Jumper (J1) and discard. The Jumper is located on the back as shown in
Figure 1B.
Figure 2. Module Mounting: