Advertisement
The radiator controller packaging contains:
Danger of suffocation!
Keep packaging materials away from children.
With the electronic radiator controller, you can set your room temperature exactly to your requirements while additionally saving energy.
Please note: The HR90 radiator controller does not directly switch your boiler on/off. It provides local room temperature control whilst the boiler is running. The boiler will be switched on/off by other controls such as timer, thermostat, etc.
User-friendly
Installation
Features for your convenience
Energy saving features
Care of use is required!
Use the radiator controller only in accordance with these operating instructions.
Do not let children play with the radiator controller.
Battery status | Meaning |
Batteries fully charged | |
Batteries half charged | |
Batteries have to be replaced soon | |
Flashing display: Batteries are dead and have to be replaced |
Ready to operate in three steps:
The radiator controller is set for the following battery type:
The language selection is only displayed during initial commissioning. During future battery changes, setting of time and date is prompted directly.
The battery life of new alkaline cells amounts to approx. 2 years. The batteries need changing when the symbol flashes. All settings are retained when the batteries are changed.
Explosion hazard!
Never charge non rechargeable batteries.
Never short-circuit batteries or throw them into fire.
Dispose of used batteries ecologically.
Checking/changing the time and date
Proceed as follows to check or to change the date and time later on:
The radiator controller can be mounted on all common thermostatic valves with an M30 x 1.5 connection without draining system.
Prevent damage to the radiator controller through humidity and moisture!
Mount the radiator controller in dry, closed rooms only.
Protect the radiator controller against humidity, moisture, dust, direct sunlight or exposure to excessive heat.
Selecting the adapter
The radiator controller fits on common radiator valves of the type M30 x 1.5. Adapters are required for some valve types.
Brand | Illustration | Adapter |
HoneywellBraukmann, MNG, Heimeier, Oventrop valves M30 x 1.5 | Not required | |
Danfoss RA | Supplied | |
Danfoss RAV | ||
Danfoss RAVL |
Mounting the valve baseplate
Mounting the radiator controller
The radiator controller only operates if it is locked correctly in the end position.
FINISHED! – After mounting, the radiator controller operates immediately in the factory setting (standard time program).
The radiator controller and the batteries can be secured against removal by using the supplied screws.
In order to improve the legibility the display of the radiator controller can be tilted to different positions (10°, 20°, 30°, 40°).
The angle of 40° can be fixed with the supplied display support.
Mounting
Unmounting
Press the display support in at the back and remove it upwards.
The following external sensors and window contacts can be connected to the HR90 radiator controller:
The ACS90 cable is required to connect external sensors and the window contact.
Operation with HCW23 setpoint adjuster
The room temperature is measured by the HCW23 setpoint adjuster. The HR90 internal room temperature sensor is not used in this particular application. The adjustment dial of the HCW23 can be used to change the room temperature ±12 K as an offset to the temperature set/programmed at the HR90. The offset setting remains valid until it is changed again.
Operation with RF20 room sensor
The room temperature is measured by the external RF20 room sensor. The HR90 internal room temperature sensor is not used in this particular application.
Operation with window contact
When the window is opened, the window contact is opened and the radiator valve closes. When the window is closed again, the radiator controller returns to normal operation.
The frost-protection function ensures that the radiator valve opens when the temperature drops below 5°C.
Cable connection
For further information also refer to the documentation for HCW23, RF20 and HCA30.
Connect the ACS90 cable as follows to the external sensor and window contact:
HCW23 setpoint adjuster
RF20 room sensor
RF20 room sensor and floating HCA30 window contact
HCA30 floating window contact
Connecting the cable with the HR90 radiator controller
In automatic mode, the radiator controller automatically controls the room temperature in accordance with the stored time program.
Week program 1: At home all day
Factory preset time program is set for each day of the week Mo – Su (1 – 7):
Setpoint | Time | Temperature |
1 | 6:00 – 22:00 | 20°C (Comfort temperature 1) |
2 | 22:00 – 6:00 | 16°C (Setback temperature) |
If you want to change the temperature specified by the time program temporarily:
Set your desired temperature using the adjustment dial.
The change remains in effect until the next setpoint.
The process of changing the temperatures permanently is described in Section 7.
In ECO mode, the room temperature in automatic mode specified by the time program is lowered by 3°C.
To activate ECO mode, press the button AUTO/ ECO/MANU until is displayed.
The displayed temperature is reduced by 3°C.
ECO mode runs until you press the button AUTO/ECO/MANU again and select a different operating mode.
In manual mode, the radiator controller operates at the (manually) set temperature until you change the temperature or change to a different operating mode.
To activate the manual mode. press the button AUTO/ECO/MANU until is displayed.
The temperature can be adjusted manually using the adjustment dial.
Manual mode runs until you press the button AUTO/ ECO/MANU again and select a different operating mode.
Selecting the "Party" or "Holiday" operating mode
Selecting the "Day off" operating mode
Three preset temperatures can be assigned to the set points in the time program:
Setting the temperatures
The three preset temperatures (Comfort temperature 1, 2 and Setback temperature) can be changed at any time.
An overview of the program structure is shown on the last page of these instructions.
Operating the radiator controller comfortably
The radiator controller can be removed from the radiator to facilitate programming.
Lost your way in the program?
Press the button AUTO/ECO/MANU is displayed. The last entry is rejected.
You can specify up to 6 setpoints per day.
The following has to be assigned to each setpoint:
Example
The example shows the following time program:
Setpoint | Time | Temperature |
1 | 6:00 – 9:00 | 20°C (Comfort temperature 1) |
2 | 9:00 – 12:00 | 16°C (Setback temperature) |
3 | 12:00 – 14:00 | 20°C (Comfort temperature 1) |
4 | 14:00 – 17:00 | 16°C (Setback temperature) |
5 | 17:00 – 22:00 | 22°C (Comfort temperature 2) |
6 | 22:00 – 6:00 | 16°C (Setback temperature) |
An overview of the program structure is shown on the last page of these instructions.
Week program
You can adjust the time program to your personal weekly routine. You have the following options to this purpose:
We recommend that you write down your time program before beginning programming.
Selecting weekdays
Editing setpoints
Editing further weekdays
Deleting a setpoint
When a setpoint is not required, select the temperature setting and confirm with .
The first setpoint cannot be deleted.
Adding a setpoint
is only displayed when less than 6 setpoints are programmed.
If several HR90 radiator controllers are to operate with the same time program, the time program only has to be created at one device (master) and can then be copied to further radiator controllers.
The ACC90 cable is required to copy the time program.
If there are no activities at one of the two radiator controllers for 4 minutes, they change automatically to automatic mode.
Copying to further devices
Terminating copying
After the last copying process has been completed:
If required, the 16 basic settings (parameters) can be adjusted. Factory settings have a grey background. Parameters marked with an * are described in more detail below.
Parameter 2 – Selecting the preset time programs
Setpoint | Time | Temperature |
1 | 6:00 – 9:00 | 20°C (Comfort temperature 1) |
2 | 9:00 – 12:00 | 16°C (Setback temperature) |
3 | 12:00 – 13:00 | 20°C (Comfort temperature 1) |
4 | 13:00 – 17:00 | 16°C (Setback temperature) |
5 | 17:00 – 22:00 | 22°C (Comfort temperature 2) |
6 | 22:00 – 6:00 | 16°C (Setback temperature) |
Setpoint | Time | Temperature |
| 6:00 to 9:00 | 20°C (Comfort temperature 1) |
| 9:00 to 13:00 | 16°C (Setback temperature) |
| 13:00 to 22:00 | 22°C (Comfort temperature 2) |
| 22:00 to 6:00 | 16°C (Setback temperature) |
Parameter 3 – Backlight
The display has a backlight for reading the information.
Parameters 5 to 7 – Window function
In order to save energy, the radiator controller closes the radiator valve when you open a window resulting in a large drop of the temperature.
When you close the window so that the temperature rises the radiator controller opens the radiator valve again.
If you should ever forget to close the window, the radiator controller opens automatically after the set time in order to ensure frost protection.
Parameter 8 – Valve stroke
The radiator controller operates with the optimum valve stroke set in the factory.
If the entire valve stroke is to be used or if the valve does not open completely, activate the full-stroke mode.
Parameter 9 – Temperature representation in the display
Parameter 12 – Optimization function
Without optimization (factory setting) the radiator controller begins to heat up the room or lower the temperature at the programmed time.
For example, in order to have a warm bathroom at 7:00, the setpoint has to be brought forward. Otherwise the room only starts heating at 7:00. However, the advanced setpoint may lie too early so that heating is started far earlier than necessary.
With optimization the radiator controller calculates when to open the valve in order to achieve the desired temperature at the set time.
Parameter 13 – Temperature offset
Since the radiator controller measures the room temperature in the area of the radiator, it is possible that this temperature deviates from the temperature measured at a different point in the room. If, for example, 20°C is measured in the room and 21.5°C at the radiator, this effect can be compensated by an offset of –1.5°C.
Parameter 15 – Display of the valve position
When this parameter is activated (setting "1"), the calculated valve position (0 to 100% opened) is displayed momentarily.
The main display is shown again after approx. 3 minutes or when the AUTO button is pressed.
Parameter 16 – Valve exercise day
If the radiator valve has not been opened once completely within the period of 2 weeks, a self-test (forced operation) is carried out. The radiator controller opens the radiator valve briefly on the subsequent Monday (factory setting) in order to prevent seizing.
The weekday for valve protection can be selected freely
Parameter 17 – Window open function
Window function
If you open a window causing the temperature to drop, the radiator controller closes the radiator valve in order to save energy. is displayed.
When the temperature rises again, but at the latest after the set period (factory setting: 30 minutes), the radiator controller opens the radiator valve again.
You can also open the radiator valve beforehand by pressing the AUTO button or turning the adjustment dial.
The sensitivity of the radiator controller to a temperature drop or temperature rise can be set, see Section 9, Parameters 5 to 7.
If a window contact is connected, the window function reacts directly to the opening and closing of the window, see Parameter 17.
Valve protection
If the radiator valve has not been opened once completely within a period of 2 weeks, a self-test (forced operation) is carried out. The radiator controller opens the radiator valve briefly on the subsequent Monday (factory setting) in order to prevent seizing. is displayed.
The day for the valve protection can be set in Parameter 16.
Frost protection
If the temperature drops below 5°C, the radiator controller opens the radiator valve until the temperature rises above 6°C again. This prevents the heating system from freezing up. frost is displayed.
The heating must be switched on to ensure the frost protection function.
If you have switched off the central heating system in summer and do not want to waste the batteries of the radiator controller, you can close the radiator valve continuously.
Closing the valve
Opening the valve
Use the AUTO/ECO/MANU button to change to automatic mode.
– or –
Set the desired temperature in manual operation.
You can block the radiator controller to protect it against unauthorized operation:
Keep the AUTO/ECO/MANU and PROG buttons pressed simultaneously for at least 3 seconds.
The symbol is displayed.
The same key combination is used to release the radiator controller again for operation.
Problem/ Display | Cause | Remedy |
flashes | Batteries flat | Replace the batteries. |
Device defective | Replace the device. | |
Motor can not be moved. | Check the installation. | |
The radiator stays hot | The radiator valve does not close fully. | Check the installation. If appropriate, change to full-stroke mode (Parameter 8). |
The room does not heat up during optimization | Heating is not switched on in time | Ensure that the precontroller switches on the heating. Synchronize the on/ off times of boiler control and radiator controller. |
Motor does not move | Valve baseplate not interlocked | Set the slider to the position . |
Type | HR90 |
Protection class | IP30 |
Supply voltage | Battery type LR6, AA, AM3 Alkaline: 2 x 1.5 V Lithium: 2 x 1.5 V NiMH: 2 x 1.2 V |
Connection to the radiator | M30 x 1.5 |
Ambient temperature | 0... 50°C |
Dimensions | 96 x 54 x 60 mm |
Ambient conditions | For living area, business and trade sections as well as small businesses |
Humidity | 10... 90% rel. humidity |
The radiator controller has to be disposed of in accordance with WEEE directive 2002/96/EC –Waste Electrical and Electronic Equipment directive.
Dispose of the packaging and product in a corresponding recycling center.
Do not dispose of the unit with the domestic refuse.
Do not burn the product.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z. A. La Pièce 16, Switzerland by its Authorized Representative
Honeywell
Honeywell House Skimped
Hill Lane Bracknell
Berkshire RG12 1EB
United Kingdom
The right is reserved to make modifications that serve improvement.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Honeywell TheraPro HR90 - Electronic Radiator Controller Manual
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the TheraPro HR90 that isn't answered in the manual? Leave your question here.