ABB PSTX30 Series Spare Part Instruction

ABB PSTX30 Series Spare Part Instruction

Replace the bypass contactor
Hide thumbs Also See for PSTX30 Series:

Advertisement

Quick Links

Softstarter type PSTX30...370
Spare part instruction - Replace the bypass contactor
1SFC132109M0201 December 2015
EN
Spare part instruction
General
For complete information, see 1SFC132081M0201 -
Softstarters Type PSTX30...PSTX1250, Installation and
Commissioning Manual available on: http://www.abb.com/
lowvoltage
1. PSTX30...105
- Replace the bypass relay
2. PSTX142...170
- Replace the bypass relay
1. PSTX30...105
1x
1x
Softstarter type PSTX30...370
2. PSTX142...170
1x
1x
Replace the bypass contactor
Service and repair should be performed by
authorized personnel only. Note that unauthorized
repair affects safety and warranty.
3. PSTX210...370
- Replace the bypass contactor
1x
Rev A
1x

Advertisement

loading

Summary of Contents for ABB PSTX30 Series

  • Page 1 General For complete information, see 1SFC132081M0201 - Service and repair should be performed by Softstarters Type PSTX30...PSTX1250, Installation and authorized personnel only. Note that unauthorized Commissioning Manual available on: http://www.abb.com/ repair affects safety and warranty. lowvoltage 1. PSTX30...105 3. PSTX210...370...
  • Page 2: Safety Information

    Safety information Warning! A qualified electrician must carry out installation, commissioning and service on the product by following installation standards and regulations. The product user hazardous voltage that can cause death or serious injury. Always disconnect power before working on equipment. Do not touch terminals when voltage is applied, output terminals can have live voltage even when the device is in off position.
  • Page 3 1. PSTX30...105 - Replace the bypass relay WARNING When performing maintenance on the Softstarter, an antistatic strap must be used. The antistatic WARNING strap should be worn on the wrist, and be Always make sure that the power supply is connected to an electrical ground, to prevent switched off before doing maintenance on the electrostatic discharge (ESD) damage to the...
  • Page 4 2. PSTX142...170 - Replace the bypass relay WARNING When performing maintenance on the Softstarter, an antistatic strap must be used. The antistatic WARNING strap should be worn on the wrist, and be Always make sure that the power supply is connected to an electrical ground, to prevent switched off before doing maintenance on the electrostatic discharge (ESD) damage to the...
  • Page 5 3. PSTX210...370 - Replace the bypass contactor WARNING When performing maintenance on the Softstarter, an antistatic strap must be used. The antistatic WARNING strap should be worn on the wrist, and be Always make sure that the power supply is connected to an electrical ground, to prevent switched off before doing maintenance on the electrostatic discharge (ESD) damage to the...
  • Page 6 Contact us ABB AB Control Products Low voltage Products SE-721 61 Västerås, Sweden Telephone: +46 (0) 21 32 50 00 www.abb.com/lowvoltage © Copyright 2015, All rights reserved. Specification subject to change without notice.