39
E L E C T R O N I C C O M PA C T S TA R T E R | M A N U A L
—
6.6
Short circuit protection
Single mounting
Single mounting means that one manual motor starter protects one HF-Starter. The maximal current of the motor defines
the size of the short circuit protection device (SCPD) and which HF-Starter is best to take.
Please find all installation proposals in table 15 for 500 V AC and table 16 for 415 V AC.
HF-Starter
Iq
[kA]
HF0.6
35
HF0.6
35
HF2.4
35
HF2.4
35
HF2.4
35
HF2.4
35
HF9
35
HF9
35
HF9
35
HF9
35
HF9
35
Table 15 Type 1 coordination of HF-Starter with Manual Motor Starter MO132 at 500 V AC
1) HF9 variants are able to switch 6.5 A in utilization category AC-53a and 9 A in AC-51.
HF-Starter
Iq
[kA]
HF0.6
70
HF0.6
70
HF2.4
70
HF2.4
70
HF2.4
70
HF2.4
70
HF9
70
HF9
70
HF9
70
HF9
70
HF9
35
Table 16 Type 1 coordination of HF-Starter with Manual Motor Starter MO132 at 415 V AC
2) HF9 variants are able to switch 6.5 A in utilization category AC-53a and 9 A in AC-51.
SCPD
Max. Current
[A]
MO132-0.63
0.075
MO132-0.63
0.63
MO132-0.63
0.63
MO132-1.0
1
MO132-1.6
1.6
MO132-2.5
2.4
MO132-1.6
1.6
MO132-2.5
2.4
MO132-4.0
4.0
MO132-6.3
6.5
MO132-10
9
1)
SCPD
Max. Current
[A]
MO132-0.63
0.075
MO132-0.63
0.63
MO132-0.63
0.63
MO132-1.0
1
MO132-1.6
1.6
MO132-2.5
2.4
MO132-1.6
1.6
MO132-2.5
2.5
MO132-4.0
4.0
MO132-6.3
6.5
MO132-10
9
2)
Max. Voltage
[V AC]
500
500
500
500
500
500
500
500
500
500
500
Max. Voltage
[V AC]
415
415
415
415
415
415
415
415
415
415
415