Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
ABB is not liable for any such damages and/or losses.
Page 6
(Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 12
Table of contents SSR5 System status register (5) device alive register....83 SSR6 System status register (6) control command status (client-dependent).................84 System diagnostic values............. 84 Time and reason for latest protection relay reset......85 User-definable bits [Alt.2], visible on 0x,1x,3x and 4x....85 User-definable registers [Alt.1], visible on 3x and 4x....86 CTRL.CBCSWI1 Circuit breaker operation counter (1) ....
Page 13
Table of contents LD0.SCA4GAPC3 Analog value scaling (3) – SCA4-3....96 LD0.SCA4GAPC4 Analog value scaling (4) – SCA4-4....97 LD0.SPEMMTR1 Single-phase power and energy measurement (1)................97 LD0.SPEMMXU1 Single-phase power and energy measurement demand values (1) – SP, SE-1......98 LD0.SPEMMXU1 Single-phase power and energy measurement (1) –...
Section 1 1MAC252756-MB B Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the protection relay. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation...
Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version History A/2018-02-26 5.0 FP1 First release B/2019-06-07 5.0 FP1 Content updated Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. REM615 ANSI Point List Manual...
Section 1 1MAC252756-MB B Introduction 1.3.3 Related documentation Name of the document Document ID Modbus Communication Protocol Manual 1MAC057386-MB Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 1 1MAC252756-MB B Introduction • Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. • Parameter values are indicated with quotation marks. The corresponding parameter values are "Enabled" and "Disabled". • Input/output messages and monitored data names are shown in Courier font.
Page 19
Section 1 1MAC252756-MB B Introduction Function IEC 61850 IEC 60617 ANSI/C37.2-2008 Overexcitation protection OEPVPH1 U/f> (1) 24-1 OEPVPH2 U/f> (2) 24-2 Negative-sequence overcurrent protection MNSPTOC1 I2>M (1) 46M-1 for machines MNSPTOC2 I2>M (2) 46M-2 Loss of load supervision LOFLPTUC1 3I< (1) 37M-1 LOFLPTUC2 3I<...
Page 21
Section 1 1MAC252756-MB B Introduction Function IEC 61850 IEC 60617 ANSI/C37.2-2008 Trip circuit supervision TCSSCBR1 TCS (1) TCM-1 TCSSCBR2 TCS (2) TCM-2 Current circuit supervision CCSPVC1 MCS 3I (1) Fuse failure supervision SEQSPVC1 FUSEF (1) Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM-1...
Page 22
Section 1 1MAC252756-MB B Introduction Function IEC 61850 IEC 60617 ANSI/C37.2-2008 Time delay on TONGAPC1 TON (1) 62TON-1 TONGAPC2 TON (2) 62TON-2 TONGAPC3 TON (3) 62TON-3 TONGAPC4 TON (4) 62TON-4 Set-reset SRGAPC1 SR (1) SR-1 SRGAPC2 SR (2) SR-2 SRGAPC3 SR (3) SR-3 SRGAPC4...
Section 2 1MAC252756-MB B Modbus data mappings Section 2 Modbus data mappings Overview This document describes the Modbus data points and structures available in the protection relay. The point lists describe a superset of all data available through the standard configuration/s including the optional functionalities.
Page 24
Section 2 1MAC252756-MB B Modbus data mappings Function IEC 61850 ANSI MA01 MA02 MA04 MA05 Positive-sequence PSPTUV 27PS undervoltage protection Negative-sequence NSPTOV overvoltage protection Three-phase remnant MSVPR undervoltage protection (source 1) Frequency protection FRPFRQ Overexcitation protection OEPVPH Negative-sequence MNSPTOC overcurrent protection for machines Loss of load supervision LOFLPTUC...
Page 25
Section 2 1MAC252756-MB B Modbus data mappings Function IEC 61850 ANSI MA01 MA02 MA04 MA05 Emergency start-up ESMGAPC 62EST Condition monitoring Circuit-breaker condition SSCBR 52CM monitoring Trip circuit supervision TCSSCBR Current circuit supervision CCSPVC Fuse failure supervision SEQSPVC Runtime counter for MDSOPT OPTM machines and devices...
Section 2 1MAC252756-MB B Modbus data mappings Function IEC 61850 ANSI MA01 MA02 MA04 MA05 Time delay off (8 pcs) TOFGAPC 62TOF Time delay on (8 pcs) TONGAPC 62TON Set-reset (8 pcs) SRGAPC Move (8 pcs) MVGAPC Generic control point (16 pcs) SPCGAPC Analog value scaling SCA4GAPC...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1 Premapped indications 2.3.1.1 Common data 1 Table 4: Common data 1 BitA RegA IEC 61850 name SA name Description Values CTRL.LLN0 2720 170.00 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2721 170.01 .LocKeyHMI.stVal.Station Station state 1=Station DR.RDRE1 2722...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.4 CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position Table 7: CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position BitA RegA IEC 61850 name SA name Description Values CTRL.CBCSWI1 POSITION 2816 176.00 .Pos.stVal.Close Close bit 1=Close 2817 176.01 .mcd 2818...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.7 CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1 Table 10: CTRL.DCSXSWI2 Disconnector position indication (2) – 29DS-1 BitA RegA IEC 61850 name SA name Description Values CTRL.DCSXSWI2 POSITION 2795 174.11 .Pos.stVal.Close Close bit 1=Close 2796 174.12...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.10 CTRL.DCXSWI2 Disconnector control (2) – 29DS-2 Table 13: CTRL.DCXSWI2 Disconnector control (2) – 29DS-2 BitA RegA IEC 61850 name SA name Description Values CTRL.DCXSWI2 POSITION 3484 217.12 .Pos.stVal.Close Close bit 1=Close 3485 217.13 .Pos.stVal.Open Open bit...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.13 CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1 Table 16: CTRL.ESXSWI1 Grounding switch control (1) – 29GS-1 BitA RegA IEC 61850 name SA name Description Values CTRL.ESXSWI1 POSITION 3496 218.08 .Pos.stVal.Close Close bit 1=Close 3497 218.09...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.33 LD0.HIBPDIF1 High-impedance differential protection for phase B (1) – 87B-1 Table 36: LD0.HIBPDIF1 High-impedance differential protection for phase B (1) – 87B-1 BitA RegA IEC 61850 name SA name Description Values LD0.HIAPDIF1 4058 253.1 .Str.general...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.37 LD0.LEDGGIO1 Indication LED states Color1/Color2 – LED These LED indication points interpret the case when a signal is wired to both the OK and ALARM inputs, but inverted to the other. This means that the LED toggles between red and green colors.
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values 3526 220.06 .LEDSt7.stVal LED 7 state 0/1=Color1/2 3527 220.07 .LEDSt8.stVal LED 8 state 0/1=Color1/2 3528 220.08 .LEDSt9.stVal LED 9 state 0/1=Color1/2 3529 220.09 .LEDSt10.stVal LED 10 state 0/1=Color1/2 3530...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values 2774 173.06 .LEDSt7.stVal LED 7 state 0/1=Off/Color 2775 173.07 .LEDSt8.stVal LED 8 state 0/1=Off/Color 2776 173.08 .LEDSt9.stVal LED 9 state 0/1=Off/Color 2777 173.09 .LEDSt10.stVal LED 10 state 0/1=Off/Color 2778...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.1.41 LD0.LOFLPTUC1 Loss of load supervision (1) – 37M-1 Table 44: LD0.LOFLPTUC1 Loss of load supervision (1) – 37M-1 BitA RegA IEC 61850 name SA name Description Values LD0.LOFLPTUC1 2912 182.00 .Str.general PICKUP Stage pickup 1=Pickup 2913...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values .mom-only Mom only alternative 3226 201.10 .Ind6.stVal X110-Input 6 State 0/1=Off/On 3227 201.11 .mcd .mom-only Mom only alternative 3228 201.12 .Ind7.stVal X110-Input 7 State 0/1=Off/On 3229 201.13...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values .mom-only Mom only alternative 3256 203.08 .SPCSO5.stVal X100-Output 5 State 0/1=Off/On 3257 203.09 .mcd .mom-only Mom only alternative 3258 203.10 .SPCSO6.stVal X100-Output 6 State 0/1=Off/On 3259 203.11...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values .mom-only Mom only alternative 3232 202.00 .SPCSO1.stVal X110-Output 1 State 0/1=Off/On 3233 202.01 .mcd .mom-only Mom only alternative 3234 202.02 .SPCSO2.stVal X110-Output 2 State 0/1=Off/On 3235 202.03...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values .mcd .ChgFlg.stVal Configuration changed 1=Changed .mcd .FacSet.stVal Factory settings in use 1=In use .mcd LD0.GNRLLTMS1 .TmChSt1.stVal Time synch. status 0/1=Down/Up .mcd LD0.SCHLCCH1 .ChLiv.stVal CH1LIV Ethernet channel 1 live 1=Live .mcd...
Section 2 1MAC252756-MB B Modbus data mappings BitA RegA IEC 61850 name SA name Description Values .SPCSO12.stVal Ouput state 12 0/1=Off/On .mcd .SPCSO13.stVal Ouput state 13 0/1=Off/On .mcd .SPCSO14.stVal Ouput state 14 0/1=Off/On .mcd .SPCSO15.stVal Ouput state 15 0/1=Off/On .mcd .SPCSO16.stVal Ouput state 16 0/1=Off/On...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.2.28 LD0.UDFCNT1 Multipurpose generic up-down counter (1) – CTR-1 Table 119: LD0.UDFCNT1 Multipurpose generic up-down counter (1) – CTR-1 BitA RegA IEC 61850 name SA name Description Values LD0. UDFCNT1 .DnCntSt.stVal DNCNT_STS Status of the down counting 1= down counting .mcd UpCntSt.stVal...
Section 2 1MAC252756-MB B Modbus data mappings 2.3.2.31 LD0.UDFCNT4 Multipurpose generic up-down counter (4) – CTR-4 Table 122: LD0.UDFCNT4 Multipurpose generic up-down counter (4) – CTR-4 BitA RegA IEC 61850 name SA name Description Values LD0. UDFCNT4 .DnCntSt.stVal DNCNT_STS Status of the down counting 1= down counting .mcd UpCntSt.stVal...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.2 Control structure 1 Table 125: Control structure 1 RegA Type Scale IEC 61850 name SA name Description Values 8001 Execute register 8002 Password reg 1 acc to setting 8003 Password reg 2 acc to setting 8004 Control register...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.5 Control structure 4 Table 128: Control structure 4 RegA Type Scale IEC 61850 name SA name Description Values 8016 Execute register 8017 Password reg 1 acc to setting 8018 Password reg 2 acc to setting 8019 Control register...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.8 Control structure 7 Table 131: Control structure 7 RegA Type Scale IEC 61850 name SA name Description Values 8031 Execute register 8032 Password reg 1 acc to setting 8033 Password reg 2 acc to setting 8034 Control register...
Page 78
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values Record 1 data to read: 9252 - Record sequence num 1...9999 9253 - Unread records left 0...499 Timestamp of record 9254 - Year, Month Year/Month 9255 - Day, Hour...
Page 79
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9279 - Millisecond Millisecond 9280 Event identification 9281 Data object ID1 9282 Data object ID2 9283 Event data value 1 9284 Event data value 2 Record 4 data to read: If selected 9285...
Page 80
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values Record 6 data to read: If selected 9307 - Record sequence num 1...9999 9308 - Unread records left 0...499 Timestamp of record 9309 - Year, Month Year/Month 9310...
Page 81
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9334 - Millisecond Millisecond 9335 Event identification 9336 Data object ID1 9337 Data object ID2 9338 Event data value 1 9339 Event data value 2 Record 9 data to read: If selected 9340...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.12 Fault record structure header Table 135: Fault record structure header RegA Type Scale IEC 61850 name SA name Description Values Selection write 9401 Read selection -99…3 Record data header 9402 Record sequence num 0...65535 9403 Unread records left...
Page 83
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9418 .FltDiskm.mag Fault distance 0.00… 9999.99 pu 9419 (Low word) 9420 .ActSetGr.stVal Active setting group 1…6 9421 .ShotPntr.stVal AR shot pointer value 0...7 Captured values during fault 9422 1000...
Page 84
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9441 1000 .APhsB1.mag Current phs B(1) 0.000… 50.000 [×In] 9442 1000 .APhsC1.mag Current phs C(1) 0.000… 50.000 [×In] 9443 1000 .ARes1.mag Current Io(1) 0.000…...
Page 85
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9464 .PPLoopReact.mag Fault loop reactance -1000.00...10 00.00 [ohm] 9465 (Low word) 9466 1000 .CBClrTm.mag Breaker clear time 0.000...3.000 9467 1000 .APhsA2.mag Current phs A(2) 0.000…...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9216 Minute 0...59 9217 Second 0...59 9218 Millisecond 0…999 1) See the technical manual. 2.4.1.16 Indication bits mirrored in registers Table 139: Indication bits mirrored in registers RegA Type Scale...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.18 SSR2 System status register (2) protection relay's mode and state Table 141: SSR2 System status register (2) protection relay's mode and state RegA Type Scale IEC 61850 name SA name Description Values 129.00 Device test mode 1=Test mode...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 130.11 < reserved > 130.12 < reserved > 130.13 < reserved > 130.14 < reserved > 130.15 < reserved > 2.4.1.20 SSR4 System status register (4) data available 2 (client-dependent, user- definable) Table 143: SSR4 System status register (4) data available 2 (client-dependent, user-definable)
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.22 SSR6 System status register (6) control command status (client- dependent) Table 145: SSR6 System status register (6) control command status (client-dependent) RegA Type Scale IEC 61850 name SA name Description Values Last cmd result code 133.00 - bit 0 133.01...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values LD0.LPHD1 2054 .NumPwrUp.stVal Num. of cold starts 0...65535 2055 .WrmStr.stVal Num. of warm starts 0...65535 2056 .WacTrg.stVal Num. of watchdog resets 0...65535 LD0.LDEV1 2057 .ChgAckCnt.stVal Num.
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.29 LD0.CMMXU1 Phase current demand values (1) – IA, IB, IC Table 152: LD0.CMMXU1 Phase current demand values (1) – IA, IB, IC RegA Type Scale IEC 61850 name SA name Description Values LD0.CAVMMXU1 Demand value 2001...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 1000 .A.phsA.cVal.mag Max demand IL1 Phs A amplitude 0.00…50.0 [xIn] 1000 .A.phsB.cVal.mag Max demand IL2 Phs B amplitude 0.00…50.0 [xIn] 1000 .A.phsC.cVal.mag Max demand IL3 Phs C amplitude 0.00…50.0 [xIn]...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.33 LD0.MDSOPT1 Runtime counter for machines and devices (1) – OPTM-1 Since the register size is 16 bits, the value saturates at 65535 hours (approximately 7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to cover the whole 300 000 hours (34 years) range.
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.36 LD0.PEMMXU1 Power measurement demand values (1) – P, E-1 Table 159: LD0.PEMMXU1 Power measurement demand values (1) – P, E-1 RegA Type Scale IEC 61850 name SA name Description Values LD0.PEAVMMXU1 Demand value 1939 .TotW.mag Active power P (high)
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.38 LD0.RESCMMXU1 Residual current demand value (1) – IG-1 Table 161: LD0.RESCMMXU1 Residual current demand value (1) – IG-1 RegA Type Scale IEC 61850 name SA name Description Values LD0.RCAVMMXU1 Demand value 1989 1000 .A.res.cVal.mag I_DMD_RES...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.40 LD0.RESVMMXU1 Residual voltage demand value (1) – VG-1 Table 163: LD0.RESVMMXU1 Residual voltage demand value (1) – VG-1 RegA Type Scale IEC 61850 name SA name Description Values LD0.RVAVMMXU1 Demand value 1977 1000 .PhV.res.cVal.mag U_DMD_RES...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 2062 .OpTmCls.mag T_TRV_CL Close travel time 0...60000 [ms] LD0.SSOPM1 0.00…99.99 2063 .TmsSprCha.mag T_SPR_CHR Spring charge time LD0.SPH1SCBR1 2064 .RmnNumOp.stVal CB_LIFE_A Remain.life phs A -/+ 9999 LD0.SPH2SCBR1 2065...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.1.44 LD0.VMMXU1 Voltage demand values (1) – VA, VB, VC Table 167: LD0.VMMXU1 Voltage demand values (1) – VA, VB, VC RegA Type Scale IEC 61850 name SA name Description Values LD0.VAVMMXU1 Demand value 1954 1000 .PhV.phsA.cVal.mag...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values - Low word .ISCS03.stVal OUT3 - Integer value 3 (high) +2147483647 - Low word .ISCS04.stVal OUT4 - Integer value 4 (high) +2147483647 - Low word 2.4.2.4 LD0.SCA4GAPC1 Analog value scaling (1) –...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.2.7 LD0.SCA4GAPC4 Analog value scaling (4) – SCA4-4 Table 176: LD0.SCA4GAPC4 Analog value scaling (4) – SCA4-4 RegA Type Scale IEC 61850 name SA name Description Values LD0.SCA4GAPC4 1000 .AnValOut1.mag AO1_VALUE Analog value 1 after scaling 0…N 1000 .AnValOut2.mag...
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values .DmdWh.actVal Accumulated Forward active 0...1E10 energy (high) , phase B [kWh] .DmdWh.actVal (low word) .DmdVArh.actVal Accumulated Forward reactive 0...1E10 energy (high) , phase B [kWh] .DmdVArh.actVal (low word)
Page 105
Section 2 1MAC252756-MB B Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values (low word) .VAr.phsC.cVal.mag Reactive power Q (high) , phase -/+ 999,999 (low word) .VA.phsA.cVal.mag Apparent power S (high) , phase -/+ 999,999 (low word) .VA.phsB.cVal.mag Apparent power S (high), phase -/+ 999,999...
Section 2 1MAC252756-MB B Modbus data mappings 2.4.2.10 LD0.SPEMMXU1 Single-phase power and energy measurement (1) – SP, SE-1 Table 179: LD0.SPEMMXU1 Single-phase power and energy measurement (1) – SP, SE-1 RegA Type Scale IEC 61850 name SA name Description Values LD0.SPEMMXU1 .W.phsA.instCVal.mag PL1-kW:1...
Section 2 1MAC252756-MB B Modbus data mappings Controls Table 180: Explanations of the controls table columns Column name Description Coil (0X) address for control value. Control structure and bit within the structure for control value. IEC 61850 name Original IED data object identification. Described in the IEC 61850 format as Logical Device.Logical Node and thereafter .Data Object.Data Attribute.
Section 2 1MAC252756-MB B Modbus data mappings IEC 61850 name SA name Description Values 2072 2.12 .RsSprChaTm.Oper.ctlVa Reset CB spring charge time 1=Reset LD0.RESCMMXU1 2073 2.13 .RecRs.Oper.ctlVal Reset Io (1) max demands 1=Reset LD0.RESVMMXU1 2074 2.14 .RecRs.Oper.ctlVal Reset Uo (1) max demands 1=Reset 2.5.2 CTRL.CBCSWI1 Circuit breaker control (1)
Section 2 1MAC252756-MB B Modbus data mappings 2.5.4 CTRL.DCXSWI2 Disconnector control (2) – 29DS-2 Table 184: CTRL.DCXSWI2 Disconnector control (2) – 29DS-2 IEC 61850 name SA name Description Values CTRL.DCCSWI2 2150 7.06 .Pos.Oper.ctlVal Select open 1=Select 2151 7.07 .Pos.Oper.ctlVal Select close 1=Select 2152 7.08...
Section 2 1MAC252756-MB B Modbus data mappings Table 187: LD0.SPCGAPC1 Generic control point (16 pcs) (1) – SPC-1 IEC 61850 name SA name Description Values LD0.SPCGAPC1 2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On 2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On 2114 5.02 .SPCS03.ctlVal...
Section 2 1MAC252756-MB B Modbus data mappings IEC 61850 name SA name Description Values 2136 6.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On 2137 6.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On 2138 6.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On 2139 6.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On 2140 6.12...
Section 2 1MAC252756-MB B Modbus data mappings 2.5.11 Unmapped control points Table 191: Unmapped control points IEC 61850 name Description Value LD0.LLN0.MeasStatRs.Oper.ctlVal Reset all min. and max. demands 1=Reset LD0.LLN0.PQRs.Oper.ctlVal Reset all power quality data 1=Reset LD0.FLTRFRC1.RcdRs.Oper.ctlVal Reset fault record data 1=Reset 2.5.12 Unmapped controls...
Section 3 1MAC252756-MB B Glossary Section 3 Glossary ANSI American National Standards Institute Electromagnetic compatibility High-speed output IEC 61850 International standard for substation communication and modeling Intelligent electronic device Light-emitting diode LHMI Local human-machine interface Modbus A serial communication protocol developed by the Modicon company in 1979.