MMU-AP___2H2UL E15-3C1 Dimensions MMU-AP0072H2UL, AP0092H2UL, AP0122H2UL, AP0072H2UL-1 7.9"(200) Check port 17.7"(450)) When a fresh-air inlet box is installed, make check port at the side of the fresh-air inlet box. Check port 17.7"(450)) 39.4"(1000) 39.4"(1000) or more or more Space required for installation 33.9"...
Page 5
E15-3C1 MMU-AP___2H2UL MMU-AP0152H2UL, AP0182H2UL, AP0212H2UL, AP0242H2UL, AP0302H2UL 7.9"(200) Check port 17.7"(450)) When a fresh-air inlet box is installed, make check port at the side of the fresh-air inlet box. Check port 17.7"(450)) 39.4"(1000) 39.4"(1000) or more or more 11.8"(300) or less Space required for installation 33.9"...
Page 6
MMU-AP___2H2UL E15-3C1 MMU-AP0362H2UL, AP0422H2UL 7.9"(200) Check port 17.7"(450)) When a fresh-air inlet box is installed, make check port at the side of the fresh-air inlet box. Check port 17.7"(450)) 39.4"(1000) 39.4"(1000) or more or more 11.8"(300) or less Space required for installation Indoor unit Ceiling bottom 33.9"...
E15-3C1 MMU-AP___2H2UL Center of gravity Total weight Model name X (In) Y (In) Z (In) Main unit Ceiling panel (lbs) (lbs) MMU-AP0072H2UL MMU-AP0092H2UL MMU-AP0122H2UL MMU-AP0152H2UL 17.9 6.05 MMU-AP0182H2UL MMU-AP0212H2UL 18.5 MMU-AP0242H2UL MMU-AP0302H2UL MMU-AP0362H2UL 17.7 7.25 MMU-AP0422H2UL MMU-AP0072H2UL-1 17.9 6.05...
MMU-AP___2H2UL E15-3C1 Piping diagram Liquid side Gas side Strainer Capillary Tube Air heat exchanger at indoor side Pulse Motor Valve Sensor (TCJ) Sensor (TC2) Sensor (TC1) Fan Motor Sensor (TA)
E15-3C1 MMU-AP___2H2UL Sound data MMU-AP0072H2UL/AP0092H2UL HH - H - L Sound pressure level (dB (A)) 32.5-30.5-29 NC-70 NC-60 4.92 ft NC-50 (1.5 m) NC-40 Microphone NC-30 Audibility limits of NC-20 continuous white level 1000 2000 4000 8000 Octave band center frequency(Hz)
Page 16
MMU-AP___2H2UL E15-3C1 MMU-AP0362H2UL MMU-AP0422H2UL H - M - L H - M - L Sound pressure Sound pressure level (dB (A)) level (dB (A)) 46-40.5-36.5 48.5-40.5-37.5 NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 Audibility limits of Audibility limits of continuous white level NC-20 NC-20...
Spacer for height adjustment TCB-SP1602UUL — Fresh-air chamber TCB-GFC1602UUL — Optional Fresh-air inlet box + TCB-GB1602UUL + — — Fresh-air chamber TCB-GFC1602UUL parts Air-discharge direction kit TCB-BC1602UUL Auxiliary fresh air flange TCB-FF101URUL *All option part is not used with MMU-AP0072H2UL-1.
4.4" (113) 24.8" (630) Ceiling bottom surface 39.4" (1000) or more 39.4" (1000) or more 24.8" (630) 27.8" (705) 3.9" (98) Space required for installation 007 to 030 type 14.0" (356) 036 to 042 type 16.5" (419) *MMU-AP0072H2UL-1 is not used.
Page 19
5.7" (144) Fresh-air chamber Ceiling bottom (Sold separately) surface 37.4" (950) 4.3" (108) NOTE This inlet box shall be used with the fresh-air chamber. 007 to 030 type 14.1" (358) 036 to 042 type 16.6" (421) *MMU-AP0072H2UL-1 is not used.
Page 20
(Implement the test run following to the installation manual of the indoor unit.) Indoor Closed end +12 V terminal P.C.board Duct fan motor Power supply of CN60 Duct fan motor (White) Relay for Closed end duct fan terminal *MMU-AP0072H2UL-1 is not used.
Page 21
Make sure it is glued properly. Indoor unit Seal heat Seal heat insulator A insulator B Dimension 3.1" (80) Unit : in (mm) 2.2" (57) Fixing hole of indoor unit 0.1" (3) 3.5" (90) Installation status of indoor unit *MMU-AP0072H2UL-1 is not used.
Page 22
39.4" (1000) or more 39.4" (1000) or more 37.8" (960) 2.0" (50) Material : Styrene foam Color : Moon white Space required for installation 007 to 030 type 8.1" (206) 036 to 042 type 10.6" (269) *MMU-AP0072H2UL-1 is not used.
Page 23
Available for all models 007 to 030 type 036 to 042 type Wind shield A 2-way air flow Wind shield C Wind shield C Available for all models Available for all models Available for all models *MMU-AP0072H2UL-1 is not used.
Page 24
Install the cover Dimension Unit:in (mm) 4.51" (114.6) 4.13" (105) 4 - Ø0.24" (6) Knockout square for branching duct 0.39" (10) 3.94" (100) in indoor unit Design sample of branching duct flange Installation sample *MMU-AP0072H2UL-1 is not used.