In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Configuration In this section you will find an overview of configuration. You are given instructions on how to configure DNP3.0 OPC Server related objects and the model of a substation or system.
The following is a list of terms associated with the DNP LAN Master OPC that you should be familiar with. The list contains terms that are unique to ABB or have a usage or definition that is different from standard industry usage.
Page 10
A communication protocol developed by Echelon. LON Application Guideline for A proprietary method of ABB on top of the standard LON pro- substation automation; LAG tocol. Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry.
LON Application Guideline for substation automation Local Area Network Logical Device LonMark interoperable device communicating in LonWorks network. In this document the term is used for devices that do not support the ABB LON/LAG communication. Logical Node LON SPA Gateway...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Abbreviation Description URCB Unbuffered Report Control Block eXtended Markup Language 1.8. Related documents Name of the manual MRS number COM600 User’s Guide 1MRS756125 1.9. Document revisions Document version/date...
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Introduction 2.1. Product overview The DNP OPC Server provides methods for OPC clients to exchange data with devices communicating via the DNP protocol. Figure 2.1-1 DNP system overview...
Page 14
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Level of Implementation DNP has three subset levels, each of which includes a specific subset of DNP message types and functionality. In COM 600 the DNP protocol has been implemented according to the Subset Level 2 of the protocol as presented in Table 2.2-1.
Page 15
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Data object Variation Description Function Qualifier Function Qualifier type code of code of code of code of Request Request Response Response message message message message 16-bit delta...
Page 16
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Data object Variation Description Function Qualifier Function Qualifier type code of code of code of code of Request Request Response Response message message message message 32-bit ana-...
Page 17
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Data object Variation Description Function Qualifier Function Qualifier type code of code of code of code of Request Request Response Response message message message message Class 0 data...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Configuration 3.1. About this section This section guides you in the configuration tasks required before you can start using the DNP OPC Server. For information on the IEC 61850 data modeling, refer to the COM600 User's Guide.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide necessary objects to the object tree in the communication structure, you need to configure them, see 3.4.1, General about configuring objects. When configuring OPC servers the following characters cannot be used in object names: \ ` ' ' # 3.3.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide To add DNP OPC Server object: 1. Select the Gateway object in the communication structure and right-click it. 2. Add DNP OPC Server object. By using the SCL Import function, it is possible to import an entire server’s or individual devices’...
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 4. Select the device to import from the drop-down list. You can preview the configur- ation on the right. 5. Click Import. The new preconfigured objects appear in the object tree. If the configuration file is very large, the import may take time.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4. Configuring objects 3.4.1. General about configuring objects After the objects have been added, you need to configure the object properties. Fig- ure 3.4.1-1 shows an example of how to use Communication Engineering Tool (CET) to configure the object properties for DNP OPC Server.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.2. Configuring DNP OPC Server properties Table 3.4.2-1 DNP OPC Server properties Property/Parameter Value or Value range/Default Description Basic Prog ID AE Instance identification of dia- gnostic OPC alarm and event server.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/Parameter Value or Value range/Default Description Header Timeout 0 to 65535 Maximum wait time in milli- seconds within which the first Default: 2000 byte of a link layer response should have been received.
Page 25
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Value or Value range/ Default Description In Use In use Controls whether the device communica- tion is initially in use or not. Not in use Default: In use...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Value or Value range/ Default Description Time Synchroniza- Direct time synchronization Function code for Time Synchronization. tion Function Delay compensated Time Synchroniza- 0 to 65535 Time in seconds between device time tion Interval updates.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide OPC Server supports three internal data object types that provide status information: • 3.4.7.2, Integer status (INS) • 3.4.7.4, Single point status (SPS) • 3.4.7.3, Controllable single point (SPC) for OPC internal data 3.4.7.2.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/Para- Value or Value range/ Default Description meter Item Tag Path Default: None Item tag path for the internal status information. The internal server tags that can be used are located in the Attributes nodes that are located under the root, line and IED nodes.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8. Configuring data objects 3.4.8.1. General about configuring data objects Object properties of the data objects are listed in the following tables. When configuring address values for DNP IED data objects, the valid address range is 0 to 65535.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8.3. Protection activation information (ACT) Table 3.4.8.3-1 Configurable ACT properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Data Class Spe- cific Control Variation 0 to 65535 Variation for control Default: 2 3.4.8.5. Binary counter reading (BCR) Table 3.4.8.5-1 Configurable BCR properties for OPC client...
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Parameter Value or Value range/ Description Default Indication Index -1 to 65535 Indication index. Default: -1 Data Class Specific Control Code Qualifier Momentary Qualifier for control.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Multiplier Default: Deka Specifies the multiplier for current SI unit. Phase Number of Default: 0 Specifies the number of decimals shown Decimals in HSI.
Page 35
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Phase BC Index -1 to 65535 Phase BC Index Default: -1 Phase CA Index -1 to 65535 Phase CA Index...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8.9. Controllable double point (DPC) Table 3.4.8.9-1 Configurable DPC properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8.10. Device Name Plate (DPL) Table 3.4.8.10-1 Configurable LPL properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic 61850 Data Object 61850 Data Object...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Indication Object Binaryinput(1,2) Object number for indication. Binaryoutput(10) Default: Binaryinput(1,2) 3.4.8.12. Controllable integer status (INC) Table 3.4.8.12-1 Configurable INC properties for OPC client...
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8.13. Integer status (INS) Table 3.4.8.13-1 Configurable INS properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Control Variation 0 to 65535 Variation for control. Default: 2 Indication Object Analog input (30, 32) Object number for indication.
Page 41
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Subtype Simple MV Sub-type Data Class Spe- cific Indication Object Analog input (30, 32) Data object number for indication.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 3.4.8.17. Controllable single point (SPC) Table 3.4.8.17-1 Configurable SPC properties for OPC client Property/ Para- Value or Value range/ Default Description meter Basic Common Data Common data class according to IEC Class 61850.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Common Data Common data class according to IEC Class 61850 Addresses Index -1 to 65535 Index. Default: -1...
Page 44
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Indication Object Analog input (30, 32) Object number for indication. Analog output (40) Default: Analog input (30, 32)
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Property/ Para- Value or Value range/ Default Description meter Default: 0 Low limit for measurement. Event is cre- ated when value crosses the limit. Low-Low Default: 0 Low-low limit for measurement.
Page 46
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Topic_generator_D3LM.png Figure 3.5-1 Default Topics Generated In most case, modifications to the automatically generated topics are not required. However, some topic definitions may need to changed, polling interval for example, in...
Page 47
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide AddTopic_D3M.png Figure 3.5-2 Add Event Poll Topic To Add an data poll topic, you may specify polling interval in hundreds of millisecond, data object type and variation, lower and upper limit of index range. If you want to poll 32 bit analog without flag every 1 second, you may setup as below in Add Topic dialog.
Page 48
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Modify_an_Existing_Topic_D3M.png Figure 3.5-4 Modify an Existing Topic To delete a topic: 1. In Topic Generator Tool, select whole row of the topic you want to delete. 2. Press Delete key from the keyboard to delete the topic.
Page 49
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Delete_a_Topic_D3M.png Figure 3.5-5 Delete a Topic...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Operation 4.1. About this section This section describes the basic operation procedures you can carry out after the server has been configured. After this, you can, for example, monitor and control network connections. This is done by using the Online diagnostics function in Communication Engineering Tool (CET).
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide dnp_serial_opc_client_ae.png Figure 4.3-1 DNP OPC Client Diagnostic AE client 4.4. DNP channel diagnostics The DNP channel activity can be monitored with the Online diagnostics function. You can also take a channel into use or out of use as described in this section.
Page 52
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide You can take device into use by marking the In use check box. If you unmark the check box, the device is taken out of use. Diagnostic counters are updated every 2 seconds. To update them manually, click Refresh.
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Technical reference 5.1. About this section This section provides reference information about the following issues: • IEC 61850 data modeling • Attributes • Status codes. 5.2. IEC 61850 data modeling 5.2.1.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 5.2.3. Double point status (DPS) Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field stVal Intermediate-state state (0=OFF, VT_I4 (0) | off (1) | on (2)
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field TimeStamp <server provided if VT_Date none> | Time of occurrence Description Text VT_Date 5.2.6.
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field TimeStamp <server provided if VT_DATE none> | Time of occurrence | MSCE 5.2.8. Device name plate (DPL)
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field hhLim REAL VT_R4 llLim REAL VT_R4 lLim REAL VT_R4 REAL VT_R4 REAL VT_R4 siUnit...
Page 58
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsB. mag AnalogueValue Phase B Current VT_R4 Value phsB.q Quality VT_I4 on-line, com lost phsB.t...
Page 59
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element neut. mag AnalogueValue Neutral Current VT_R4 Value neut.q Quality VT_I4 on-line, com lost neut.t TimeStamp VT_DATE neut.range...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 5.2.13. Delta (DEL) Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsAB. mag AnalogueValue Phase AB Current VT_R4 Value phsAB.q Quality VT_I4 on-line, com lost phsAB.t...
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP information OPC data types ory/Optional element phsCA. mag AnalogueValue Phase CA Current VT_R4 Value phsCA.q Quality VT_I4 on-line, com lost phsCA.t...
COM600 Station Automation Series 1MRS756566 DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide 5.2.15. Controllable double point (DPC) Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field stVal BOOLEAN FALSE | TRUE State (0:OFF, VT_BOOL 1:ON)
1MRS756566 COM600 Station Automation Series DNP 3.0 LAN/WAN Master (OPC) 3.2 User's Guide Name Type Value/Value range Mandat- DNP data object OPC data types ory/Optional field Quality DNP status VT_I4 TimeStamp <server provided if VT_DATE none> | Time of occurrence | MSEC...