Page 2
Important Please Read Before Starting When Installing …………………………………………………………………… …In a Room This air conditioning system meets strict safety and Properly insulate any tubing run inside a room to prevent operating standards. As the installer or service person, it “sweating” that can cause dripping and water damage to is an important part of your job to install or service the walls and floors.
Page 3
Check of Density Limit Do not install the indoor unit NOTE 2 : The standards for minimum room to the place, such as a volume are as follows. basement, etc. where No partition (shaded portion) refrigerant can stay, since refrigerant is heavier than air. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed...
Contents Page Please Read Before Starting Important............. i Check of Density Limit Important ..............ii Section 1 : Outline of W-ECO MULTI SYSTEM ........I - 1 1. Line Up ....................... I - 2. Features of W-ECO MULTI SYSTEM ..............I - 3.
Page 5
Contents Page Section 6 : Processes and Functions ..........VI - 1 1. Compressor Control .................... VI - 2 2. Protection Controls ..................... VI - 3 3. Fan Control ......................VI - 5 4. Outdoor Electronic Expansion Valve ..............VI - 5 5.
Page 6
Outline of W-ECO MULTI SYSTEM Contents 1. Outline of W-ECO MULTI SYSTEM 1. Line Up ....................I - 2 2. Features of W-ECO MULTI SYSTEM ..........I - 4 2-1. Outline of system ............................I - 4 2-2. Installation ..............................I - 7 2-3.
Limitation of system Connection Allowable no. outdoor unit connected 2 units SANYO makes it possible to link Allowable max. capacity of outdoor unit 30 H.P. (84 kW) outdoor units together for a large Allowable No. of indoor unit connected 32 units 84 kW (30 H.P.) capacity (the largest in...
Outline of W-ECO MULTI SYSTEM 2. Features of W-ECO MULTI SYSTEM 7 Capacity control With a triple compressor organization (consisting of one PC compressor and two AC compressors), capacity control can be implemented by adding an external save valve. To Indoor Unit Narrow tube (H.P.) Wide tube...
Page 11
Outline of W-ECO MULTI SYSTEM 2. Features of W-ECO MULTI SYSTEM 7 Control system diagram The indoor and outdoor units each have communications • The main bus is twin-core and non-polar for easier wiring. terminals that allow connection of as many as 94 units •...
Outline of W-ECO MULTI SYSTEM 2. Features of W-ECO MULTI SYSTEM 2-3. Control characteristics 2-2. Installation 7 New control wiring system (S-net link 7 Compact size and Light weight outdoor unit system) 150 Type 190 Type 70 Type 90 Type ¶...
Outline of W-ECO MULTI SYSTEM 2. Features of W-ECO MULTI SYSTEM 2-4. Delicate control with large crystal display 7 Remote controller (RCS-SH80TG) 7 “Personal” comfortable air flow : Option ¶ Comfortable auto flap control • The flap is automatically positioned moving it AIR FLOW upward / downward, at the time of switching over CENTRAL CTRL...
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Unit 7 Whisper-quiet operation 3-1. 4-Way air discharge semi- concealed type The noise level of Type 12, 18, 25 has reduced to 37 dB (A) in the “Hi” mode and 31 dB (A) in the “Lo” mode. XR123GH, XR183GH, XR253GH, Thanks to the newly developed turbo fan and decreased XR363GH, XR483GH...
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Unit 7 Ideal air stream realized for both heating 3-2. 2-Way air discharge semi- and cooling. concealed type Comes with auto flap feature SR93GH, SR123GH, SR183GH, SR253GH as standard. S93GH, S123GH, S183GH, S253GH When the fan speed be- comes Lo at the time of heating, the auto flap adjusts...
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Unit ¶ Sophisticated Color and Round Surface Design 3-4. Wall-mounted type ¶ Simple installation work ¶ 3-way tubing possible KR93GH, KR123GH, KR183GH K93GH, K123GH, K183GH Left tubing Left-rear tubing Right-rear tubing (recommended) 1273_K_I ¶...
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Units ¶ Built-in drain pump 3-6. Concealed-duct type One of the major features of the new concealed-duct UR93GHN, UR123GHN, UR183GHN, type air-conditioner is that air flow outlets can be UR253GHN, UR363GHN, UR483GHN arranged individually using circular flexible ducts.
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Units Flat appearance and easy to maintain. 3-8. Floor-standing type (F Type) ¶ Front panel opens fully for easier maintainance. FR93GH, FR123GH ¶ Removable air discharge grille allows changing air FR183GH, FR253GH flow direction.
Outline of W-ECO MULTI SYSTEM 3. Outline of Indoor Units 3-10. 1-Way air discharge semi-con- Super-slim 19.8 cm design cealed slim type ¶ With an embedded area of just 19.8 cm, it is ideal for installation in areas with limited space. Plus, the SLR93GH, SLR123GH ceiling panel is just 1.5 cm deep, so it doesn’t impose SLR183GH, SLR253GH...
Outline of W-ECO MULTI SYSTEM 4. Example of W-ECO MULTI SYSTEM 4-1. List of controllers Ref. page Name Features III-6~ 1 Group (collective) control of maximum up to 8 indoor units with a Remote Controller RCS-SH80TG remote controller is possible. 2 Control with multiple remote controls (main / sub) is possible.
Page 21
Outline of W-ECO MULTI SYSTEM 4. Example of W-ECO MULTI SYSTEM Name Ref. page Features III-62~ 1 This easy-to-operate, multifunction remote controller is ideal for use Simplified Remote Controller RCS-KR1T in hotels and large facilities not requiring precise temperature control. 2 Basic functions include Start/Stop, Mode selection, Temperature and Fan Speed/Airflow settings.
Outline of W-ECO MULTI SYSTEM 4. Example of W-ECO MULTI SYSTEM 4-2. Example of control system Contents of control Controller Control method Remote (1) Standard control (1) Standard control ¶ The cooling / heating mode of controller RCS-SH80TG (2) Multiple remote control outdoor unit is determined by the first-press priority of remote controller.
Design of W-ECO MULTI SYSTEM Contents 2. Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation ........II - 2 1-1. Operating range ............................II - 2 1-2. Procedure for selecting models and calculating capacity ................II - 3 1-3.
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-1. Opertating range Heating Cooling 15.5 Operating Operating range range –5 –10 –15 Indoor air intake temp. °C (DB) 606_8132 –5 –10 : Rated conditions Indoor air intake temp. °C (WB) 1750_M_I Cooling operating range NOTE...
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-2. Procedure for selecting models and calculating capacity Select the model and calculate the capacity by using the procedure below. ¶ Calculate the maximum air-conditioning load of each room or zone. Calculation of the indoor air-conditioning load ¶...
Page 26
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-3. Calculation of actual capacity Since the capacity of multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference, etc. select the right model taking into account various correction values. 7 The actual capacity of multi air-conditioner according to its installation conditions is given by the following expression.
Page 27
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 7 Outdoor unit capacity when the indoor / outdoor capacity ratio is in the range of 100 % to 130 % The outdoor unit capacity, in case the indoor / outdoor capacity ratio is 100 % - 130 %, can be found out from the table of corrected capacities given the graph shown Cooling...
Page 28
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation ¶ Corrected capacity of indoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100 to 130 % Unit: kW Indoor Unit Unit 9 type 12 type 18 (K) type 18 type (except K)
Page 29
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation ¶ Corrected capacity of outdoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100 to 130 % PC units 150 type 190 type Capacity kW Capacity kW Indoor / Outdoor unit capacity ratio...
Page 30
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-4. Capacity correction graph according to temperature condition (For R407C) Cooling capacity diagram Heating capacity diagram 15°C a. b 22°C c. d. e a. b c. d. e 22°C a.
Page 31
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-5. Capacity correction graph according to refrigerant tubing length and elevation difference (For R407C) Cooling capacity coefficient 120 125 Total equivalent tubing length (m) 1529_M_I To minimize the reduction in cooling capacity to be caused when an excessively long tubing is used, we recommended increasing the diameter of the wide tubing as indicated in Table 1.
Page 32
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-6. Capacity correction graph according to temperature condition (For R22) Cooling capacity diagram Heating capacity diagram 15 °C a. b 22 °C c. d. e a. b c. d. e 22 °C a.
Page 33
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-7. Capacity correction graph according to refrigerant tubing length and elevation difference (For R22) Cooling capacity coefficient 86 84 82 80 78 74 72 70 68 66 110 120 125 Total equivalent tubing length (m) 726_8132 Heating capacity coefficient...
Page 34
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 1-8. Design of tubing length < = 1. Main tube LM = LA + LB... 50 m. 2. Size of main tube after distribution joint LC ...is depend on the capacity after distribution. 3.
Page 35
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation Tubing size Main tubing size (LA, LB, LC...) Unit: mm (in.) 40.0 kW or more 52.4 kW or more 70.0 kW or more Combination Capacity of Outdoor Unit less than 52.4 kW less than 70.0 kW less than 106.0 kW Main tube size...
Page 36
12.7 * Always recharge accurately using a scale for weighing. 15.88 19.05 22.22 25.4 Refrigerant charge amount at shipment. R407C models PC unit AD unit R407C SPW-CR1503GDYH8 SPW-CR1903GDYH8 SPW-CR703GDCH8 SPW-CR903GDCH8 (kg) 16.5 R22C models PC unit AD unit SPW-C1503GDYH8 SPW-C1903GDYH8...
Page 37
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation 7 Recommended location of ball valves ¶ Recommend that install a ball valve kit at each outdoor unit ¶ Select the position to perform the service easily each unit or each refrigerant system (1) In case of adding the indoor unit 1 LOCATION: Install the ball valve at distribution tube (not main tube).
Page 38
Design of W-ECO MULTI SYSTEM 1. Model Selecting and Capacity Calculation Always check the gas density for the room in which the unit is installed. 7 Check of limit density Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the When installing an air-conditioner in a room, it is neces- following table.
Design of W-ECO MULTI SYSTEM 2. Example of System Design 2-1. Example of tubing size selection and additional charge amount Outdoor unit to be installed additionally Indoor unit to be = 2 m = 1 m installed additionally LA = 20 m LF = 5 m LB = 5 m LC = 6 m LD = 6 m LE1 = 0.4 m...
Page 40
Design of W-ECO MULTI SYSTEM 2. Example of System Design After extending indoor and outdoor unit 1× × × × × 2 1 Tubing 2 Additional Total cooling capacity after distribution joint Wide tube Narrow tube / Outdoor unit type / Indoor unit type length (m) refrigerant (g/m) (g) 10.6 + 7.3 + 7.3 = 25.2 kW...
45 A 50 A 14 mm (AWG #6)* SPW-C903GDCH8 6 mm 39 m 50 A 50 A 14 mm (AWG #6)* SPW-CR1503GDYH8 10 mm 36 m 60 A 80 A 22 mm (AWG #4)* SPW-CR1903GDYH8 10 mm 35 m 80 A...
Design of W-ECO MULTI SYSTEM 3. Electrical Wiring 3-3. Wiring system diagrams Indoor unit (No. 1) Power supply Outdoor unit 220-240V 50Hz PC unit Ground Power supply 380-415V-3N 50Hz Remote controller Ground Ground Ground Indoor Ground unit (No. 2) Power supply 220-240V 50Hz Outdoor unit...
Page 43
Design of W-ECO MULTI SYSTEM 3. Electrical Wiring CAUTION (1) When linking outdoor units in a network (S-net link system), remove the short plug (CN031, 2P Black, location: right bottom on the outdoor control PCB) from all outdoor units except any one of the out- door units.
Page 44
Design of W-ECO MULTI SYSTEM 3. Electrical Wiring (5) Use shielded wires for inter-unit control wiring (c) Shielded wire and ground the shield on both sides, otherwise misoperation from noise may occur. All wiring except inter-unit control wiring (c) has ground ground polarity.
Page 45
Design of W-ECO MULTI SYSTEM 3. Electrical Wiring 3-4. Maximum power input ¶ The maximum power input of the outdoor unit is a electric power input consumed when the outdoor unit is oper- ated under the condition of the JIS cooling overload at the indoor / outdoor unit capacity ratio of 130 %. ¶...
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-1. Selecting the installation site Ceiling-Mounted Type Indoor Unit Ceiling AVOID: areas where leakage of flammable gas may be expected. Wall places where large amounts of oil mist exist. min. 25 cm min.
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-2. Transporting When transporting the unit, have it delivered as close to Rope or strap the installation site as possible without unpacking. Use hook for suspending a unit type 190 and 150.
Page 48
Design of W-ECO MULTI SYSTEM 4. Installation Instructions (2) The types 70 and 90 must be bolted down through PC unit AD unit (132) vibration insulators tightly to the blocks or platform with 4 anchor bolts. The unit must sit on the vibra- CAUTION tion insulator and platform at least 10 mm wide at both ends.
Page 49
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-4. Outdoor Unit AVOID: heat sources, exhaust fans, etc. Exhaust fan damp, humid or uneven locations. Hot air Indoor (no ventilation place) Heat source Out- door choose a place as cool as possible. unit choose a place that is well ventilated.
Page 50
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-5. Shield for horizontal exhaust dis- charge It is necessary for you to install an air-discharge chamber (field supply) to direct exhaust from the fan horizontally if it is difficult to provide a minimum space of 2 m between the air- discharge outlet and a nearby obstacle.
Page 51
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-8. Dimensions of snow / wind ducting Reference diagram for air-discharge chamber (field supply) 1081 1776_C_I TD831077 II - 29...
Page 53
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-9. Dimensions of wind ducting Reference diagram of air-discharge chamber (field supply) PC (power control) unit 1100 2050 1678_C_I AD (additional) unit 1100 1679_C_I TD831077 II - 31...
Page 54
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-10. Dimensions of snow ducting Reference diagram for snow-proof vents (field supply) PC (power control) unit 1100 2050 2050 1751_C_I AD (additional) unit 1100 1752_C_I TD831077 II - 32...
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-11. Optional distribution joint kits See the installation instructions packaged with the distribution joint kit for the procedure for installation. Model Name Cooling capacity after distribution 1. APR-HV63MB1 16.0 kW (54.6 Mbtu/h) or less 2.
Page 56
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4. APR-HV84MB Part name Distribution joints Insulations Joint Figure 1688_M_I 110 110 110 120 110 110 110 120 1630_M_I 1628_M_I 1629_M_I Q’ty Size of connection point on each part (Part A-G show inside diameters of tubing and Part Z shows outside one.) Size Part A Part B...
Page 57
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 7. APR-DV148MB Part name Distribution joints Insulations Reducing joints Figure 1641_M_I 1640_M_I 1642_M_I 1643_M_I 1639_M_I Q’ty Figure 1646_M_I 1647_M_I 1645_M_I 1644_M_I Q’ty Size of connection point on each part (Part A-L show inside diameters of tubing and Part X-Z show outside ones.) Size Part A Part B Part C Part D Part E Part F Part G Part H...
Page 58
Design of W-ECO MULTI SYSTEM 4. Installation Instructions 4-12. Optional ball valve kits See the installation instructions packaged with the ball valve kit for the procedure for installation. Model name Contents Applicable Indoor unit cooling capacity outdoor unit after the ball valve for R407C for R22 Ball valve mm (inch)
Control of W-ECO MULTI SYSTEM Contents 3. Control of W-ECO MULTI SYSTEM 1. Main Operating Functions .............III - 2 1-1. Room temperature control ..........................III - 2 1-2. Fan speed control ............................III - 2 1-3. Auto flap control .............................III - 3 1-4.
Control of W-ECO MULTI SYSTEM 1. Main Operating Functions 1-1. Room temperature control The thermostat turns ON / OFF with the following ∆T. (2) Fan operation : Set fan speed (3) Dry operation : L ∆T = Room temp - Set temp (4) When thermo.
Control of W-ECO MULTI SYSTEM 1. Main Operating Functions ¶ Heating operation control 1-3. Auto flap control 1 During heating operation, the “Set fan speed” [Applicable indoor units] is set as follows after the thermostat turns ON. 4-Way, 2-Way, & ceiling mounted E2 Temp ¶...
Control of W-ECO MULTI SYSTEM 1. Main Operating Functions 1-4. Functions for group control & multiple remote control Group control and multiple remote control become possible by using remote controllers; however part of the functions of the main and sub remote controller cannot be controlled. So, confirm them referring to the following table. Individual remote control (standard) Group control Multiple remote control...
Control of W-ECO MULTI SYSTEM 2. Optional Controller 7 List of optional controller functions ¶ Remote controller functions In multi system, the following optional remote controllers can be selected, but there are some functions which cannot be controlled. So, confirm the usable functions from the following table at the time of selecting them. : Controllable : Uncontrollable Remote...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 2-1. Remote controller / RCS-SH80TG 7 How to use the remote controller C: MODE button AIR FLOW CENTRAL CTRL UNIT MODE UNIT No. K: UNIT button D: Temperature STANDBY H: FLAP button R.C.
Page 65
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) FAN SPEED button The air conditioner automatically decides the fan speed. High fan speed Medium fan speed Low fan speed button Use this button to reset the filter sign (timer). (Filter) The air conditioner has the timer for filter and informs you the time of cleaning the filter.
Page 66
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Display (Remote controller) AIR FLOW CENTRAL CTRL UNIT MODE UNIT No. STANDBY R.C. FLAP MODE FIXED °C SET TEMP. CODE TIMER SET SWEEP SET TEMP. FAN SPEED SETTING CHECK DATA MONITOR SERVICE TEST...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Setting the Timer Use this mode to turn off the appliance automatically after the length of time set. OFF timer Set time 755_8132 Use this mode to start the appliance automatically after the ON timer length of time set.
Page 68
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) How to set the OFF timer ( (Example) To stop the air conditioner after 3:30. Operation Indication 1. Press the ON / OFF button to start the air conditioner. 2. Press the TIMER SET button to and time indications SETTING SETTING...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 How to install the remote controller Remote controller wiring can be extended to a maximum Do not supply power to the of 1,000 m. unit or try to operate it until CAUTION the tubing and wiring to the ¶...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Basic wiring diagram ¶ Use shielded wires for inter-unit control wiring and Install wiring correctly ground the shield on both sides. (incorrect wiring will damage the CAUTION Otherwise misoperation because of noise may occur. equipment).
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Wiring system diagram for group control This diagram shows when several units (maximum of 8) are controlled by a remote controller (master unit). In this case, a remote controller can be connected at any indoor unit. Remote controller Wiring procedure...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Wiring system diagram for multiple remote control ¶ When Installing Multiple Remote Controllers This multiple remote controller system is used for operating the unit(s) at different positions. (A maximum of 2 remote controllers can be installed.) ¶...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Service functions of remote controller From the remote controller you can control both the operation and settings of the unit as well as perform several useful service checks. This section explains how to use the remote controller to: (A) Set service check switches.
Page 74
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) (B) Use the test run procedure The purpose of the test run function is to let you control the operation of the unit directly without the thermostat turning the unit on or off. As indicated in the following procedure, be sure to switch out of TEST RUN when you are finished, or the air conditioner can be damaged because it won’t cycle on and off normally.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Check the sensor temperature readings The air conditioner has temperature sensors placed in areas where temperature levels control the heating or cooling process. Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor unit address is used only when several units are hooked up to one remote controller (group control).
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Refer to the table below for the relationship between the sensor address and the location of the sensor. Relationship between the sensor address and the location of sensor Sensor Address Location of Sensor (Themistor) (CODE No.) Indoor Unit...
Page 77
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) The panel now shows this display as shown below. UNIT No. UNIT No. 1–1 R.C. CODE Refrigerant Circuit No. CODE No. CHECK Alarm message SERVICE 778 _8132 A maximum of 4 alarm messages can be accessed by pressing either SET TEMP button j or l as follows. MODE NOTE Pressing CL (Clear) button will clear all Past...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Important Never press CL button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. To erase accessed data, press the CL button. When erasing is finished, ---- shows on the controller’s display.
Page 79
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) (F) Execute the auto. address operation Auto. address operation is executed by pressing the A. ADD button of outdoor unit’s PCB usually (See “Test Run” V-2 ~). For your convenient it can be executed by remote controller also. Press the TEST / CHK and ) buttons at the same time for more than 4 seconds.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) (G) Confirm and change the indoor unit address The purpose of the above function is to let you confirming the indoor unit address after the auto. address operation, and changing the indoor unit address if it is needed. Press the TEST / CHK and ) buttons at the same time for more than 4 seconds.
Page 81
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Set the required new indoor No. by pressing the ) button. AIR FLOW UNIT MODE Ex: UNIT No. 3-6: current registed the indoor unit address R.C. FLAP SET TEMP. CODE TIMER SET FAN SPEED SETTING...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) (H) Change the shift temperature in heating mode If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off early in heating mode because of the hot air temperature of ceiling level. In order to resolve the problem, the shift temp. (valid while heating only) is set when shipped from factory (refer to room temp.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) ( I ) Set the indoor unit address This function is usable if the auto. address operation is not possible. Indoor unit address can be set one by one by remote controller in such case. NOTE 1) In case of group control, branch wiring for group control should be removed temporarily.
Page 84
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Set the No. of R. C. which you want to set with ) button. Ex. No. of R. C. will be set 2. AIR FLOW UNIT MODE UNIT No. R.C. FLAP SET TEMP.
Page 85
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Select the code No. 14 to set group setting with the (SET TEMP) button. Set the No. of group setting as shown below with the ) button. 0 : Standard system (except group control) AIR FLOW UNIT MODE...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) (J) Change the period of the filter timer If the period of filter timer is not suitable (for example in case of dirty environment), the period can be half done as follows: Press the TEST / CHK button for more than 4 seconds.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) 7 Explanation of alarm messages Alarm Possible cause of malfunction message Error in receiving serial communication signal. Remote controller is detecting Serial (Signal from main indoor unit in case of group control) error signal from indoor unit.
Page 88
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote controller) Alarm Possible cause of malfunction message Indoor thermistor is either open Thermistor Indoor coil temp. sensor (Sensor no. 03, TH2) <<F1>> or damaged. fault Indoor coil temp. sensor (Sensor no. 04, TH3) <<F2>>...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 2-2. System controller / SHA-KC64TG ALL / ZONE / GR SELECT MODE ZONE °C ZONE SET TEMP. SET TEMP. GROUP FAN SPEED CENTRAL CTRL CENTRAL CTRL FLAP • • TEST / CHK 668 _8132 ¶...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 How to use the system controller A: ALL / ZONE ALL / ZONE / GR / GROUP ZONE SELECT MODE F: MODE button GROUP SELECT button STANDBY ZONE MODE FIXED B: ZONE select °C ZONE...
Page 91
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 Function of buttons (Continued) D: ON/OFF operation button This button is for turning the selected air conditioner(s) on and off. E: Operation lamp This lamp lights when the appliance is turned on. F: MODE button Use this button to select one of the following four operations: (AUTO)
Page 92
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) K: CENTRAL CONTROL button Use this button to inhibit individual operation by remote controller for central control as follows: CENTRAL CTRL 1 : Inhibiting individual ON / OFF operation 2 : Inhibiting individual ON / OFF, MODE and SET TEMP operation. 3 : Inhibiting individual MODE and SET TEMP operation.
Page 93
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) Display ALL / ZONE / GR ZONE SELECT MODE GROUP STANDBY ZONE MODE FIXED °C ZONE SET TEMP. SET TEMP. CHECK GROUP FAN SPEED SWEEP CENTRAL CTRL CENTRAL TEST CTRL FLAP CENTRAL CONTROL •...
Page 94
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) How to start individual operation To start individual operation Press the SELECT button Keep the power supply and select GROUP. switch turned on more Power than 5 hours before Select the ZONE No. starting operation.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 How to install the system controller Installation site selection Do not supply power to the Install the system controller at a height of between 1 unit or try to operate it until and 1.5 meters above the floor.
Page 96
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) Diagram of outer dimensions Electrical component box Hole for electrical Control unit Unit: mm wiring Mounting plate (for flush mounting) 4-ø 5 diameter holes (for mounting) 0215_M_I Hole for electrical wiring Rear plate 0216_M_I 4-ø...
Page 97
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) Installation procedure Mounting plate Electrical component box Hole for electrical wiring a): Normal mounting Rear plate b): Flush mounting 0217_M_I 1. Decide how the system controller will be mounted: in the normal manner or flush with the wall.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 Layout of electrical terminals Clamp for electrical wiring Connector (CN02) for weekly timer (TM-WBGN: optional) CN02 Ground for P.C board power wiring L (L1) N (L2) B3 B2 B1 A3 A2 A1 1789_M_I How to connect electrical wiring 1) Basic wiring...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 Basic wiring diagram Make correct wiring without any mistakes (incorrect CAUTION wiring will damage the equipment). Outdoor Outdoor Outdoor Outdoor unit–1 unit–2 unit–3 unit–m > • • • System controller Power supply 220-240V 50Hz...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 Control with multi (main / sub) This controll is used for operating the unit(s) with multiple system controllers (up to two). system controllers Address switch Bit No. System controller operates as System controller operates as sub-controller main controller...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) 7 How to set zone registration To operate system controller properly, zone registration is required after finishing test run (after setting all indoor unit addresses) as following methods. (1) Zone registration by remote controller (RCS-SH80TG) (2) Zone registration by system controller (SHA-KC64TG) (3) Auto.
Page 102
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) ZONE registration table Indoor unit Indoor unit Central Central address address ZONE GROUP Unit location ZONE GROUP Unit location address address (UNIT No.) (UNIT No.) NOTE You should assign each indoor unit address to the desired position (Central ad- dress) manually.
Page 103
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) (1) Zone registration by remote controller (RCS-SH80TG) In this case confirming the indoor unit connected with the remote controller, you set the central address one by one. In case of remote controller–less system, connect remote controller to the system temporarily then follow this procedure.
Page 104
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) Set the central address which you want to set to this indoor unit address with ) button according to the zone registration table For example, in case of left Indoor unit address : 1–8 AIR FLOW Central address : 17 (ZONE 2, GROUP 1)
Page 105
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) (2) Zone registration by system controller In this case you set all central addresses by system controller at once manually. Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. SETTING and CODE No.
Page 106
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) Select the zone and group No. which you want to set with ZONE and (GROUP) buttons. Set the UNIT No. (Indoor unit address) with FAN SPEED and FLAP buttons according to the zone registration table.
Page 107
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) (3) Auto. zone registration by system controller Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. and CODE No. C1 will flush. SETTING Select CODE No.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (system controller) How to check overlapping of central address No. Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. SETTING and CODE No. C1 will flash. Select CODE No.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 2-3. Weekly timer / TM-WBGN Su Mo Tu We Th Fr Sa CHECK PROGRAM PROGRAM ERROR PROGRAM 1 CANCEL PROGRAM 2 PROGRAM 3 CLEAR CLOCK 682 _8132 ¶ The weekly timer is used, connected to remote controller (RCS-SH80TG), and system controller (SHA-KC64TG). ¶...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 7 How to use the weekly timer PROGRAM button Used to set the program operation CHECK button DAY button Used to check the Su Mo Tu We Th Fr Sa operation reservation.
Page 111
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) (B) Setting the day (A) Setting the current time ¶ Set today’s day. (Ex: On Wednesday) ¶ Set the current time. (Ex: When the current time is 1 Holding the SET button pressed, press the DAY 11 hrs.
Page 112
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 1 At first, press the program button. 4 Set the OFF time by pressing the HH. and MM. buttons, and press SET button. ¶ The operation reserva- tion display “ ” starts flashing as soon as the Su Mo Tu We Th Fr Sa CHECK...
Page 113
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 6 Finally, press the PROGRAM button. (D) Set error After setting, press the PROGRAM button within the next 30 seconds. If the “ERROR” starts flashing at the time of setting program operation, correct the time in the following way.
Page 114
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) NOTE ¶ “ERROR” is displayed, if the ON / OFF times are set as follows. (1) If the operating times overlap 0:00 23:59 1050_1143 (2) If the OFF time is earlier than the ON time 0:00 23:59 1051_1143...
Page 115
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) (E) Copying the program operating time 2 Press DAY button, and bring the operation reserva- tion indicator “ ” at the day to be checked. At the time of setting program operation, if the operating time to be set is the same as that an already set ¶...
Page 116
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) ¶ Description of operation (H) Clearing a program operation The operation is temporarily cancelled on the day ¶ Clearing the program of the day which is set as a cancel day, but on the following day the cancel set indicator “I I”...
Page 117
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) (J) Others Some information on this weekly timer 1. Power Failure If a power failure occurs during operation, and the power Su Mo Tu We Th Fr Sa PROGRAM CHECK supply is later recovered, the display appears as shown PROGRAM ERROR...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 7 How to install the weekly timer Switch box for 1 (no cover) or switch box for 2 (no cover) Do not supply power to the unit or try to operate it until Spacer the tubing and wiring to the M4 ×...
Control of W-ECO MULTI SYSTEM 2. Optional Controller (weekly timer) 7 Wiring diagram 7 Test run setting (for wiring, always use the supplied wires) ¶ After installation, check the output state of the weekly timer with the “FORCED OPR.” switch (OFF to ON) located on the rear side of its PCB.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (simplified remote controller) 2-4. Simplified remote controller / RCS-KR1TG 7 How to use the simplified remote controller CENTRAL CTRL STANDBY °C SET TEMP. TEST SETTING CHECK SENSOR FAN SPEED SET TEMP. C: Temperature D: FAN SPEED setting buttons selector button...
Page 121
Control of W-ECO MULTI SYSTEM 2. Optional Controller (simplified remote controller) FAN SPEED selector button (AUTO) The air conditioner automatically decides the fan speed. (HI.) High fan speed (MED.) Medium fan speed (LO.) Low fan speed FLAP button 1. Use this button to set the airflow direction to a specific angle. ¶...
Page 122
Control of W-ECO MULTI SYSTEM 2. Optional Controller (simplified remote controller) Display (Remote controller) CENTRAL CTRL STANDBY °C SET TEMP. TEST SETTING CHECK SENSOR FAN SPEED SET TEMP. ON - / OFF - MODE FLAP TEST 1505_T_I Description A : This is displayed to indicate that the system controller is being used for control. When is flashing on the display, the operation is not accepted by the system controller.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (simplified remote controller) 7 How to install the simplified remote controller When connecting the locally supplied three core lead wires to the terminal block, check the terminal numbers in the indoor unit to make Do not supply power to the sure that the wires are correctly connected.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (simplified remote controller) 7 Basic wiring diagram Make correct wiring without any mistakes (incorrect CAUTION wiring will damage the equipment). ¶ Following is a wiring diagram for controlling one indoor unit by two simplified remote controllers. Simplified remote Simplified remote controller (main)
Control of W-ECO MULTI SYSTEM 2. Optional 2-5. Indoor-use Relay Board / ACC-DC24SB Used for centralized control over various air conditioner operations from a remote location. Can be connected to all ECO indoor units. Input Indoor Board Relay Board Remote Board 3P/10P ¶...
Page 126
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote sensor) 7 How to install the remote sensor When connecting the remote sensor wires, check the terminal num bers in the indoor unit Do not supply power to the to make sure that the wires are correctly con unit or try to operate it until nected.
Page 127
Control of W-ECO MULTI SYSTEM 2. Optional Controller (remote sensor) 7 How to wire the remote sensor ¶ Connection diagram Approximately 200 mm Terminal block 3P-1 for wiring the 3P-2 remote Remote sensor controller of 3P-3 ∗1 the indoor unit Power supply from remote sensor body Connector Remote sensor wiring (supplied locally)
Page 128
Control of W-ECO MULTI SYSTEM 2. Optional Controller (S-DDC) 7 How to install the S-DDC (SHA-KD2000TG) Hook the AMY adapter to the fixture 7 Accessories Accompanying parts Q’ty Accompanying parts Q’ty Fixture Nylon clamper TYPE 3 TYPE 4 Screws (4 × L12) RS-232C cable For fixture Screws for...
Page 129
Control of W-ECO MULTI SYSTEM 2. Optional Controller (S-DDC) 7 Wiring diagram (2) Connecting control wires. Use two-core, 0.5 mm to 1.6 mm lead wire for AMY and inter-unit control wiring for AMY adapter AMY control wire. The limited length of control wire should be wired as shown below.
Page 130
Control of W-ECO MULTI SYSTEM 2. Optional Controller (S-DDC) ¶ RS-232C cable (2) Branch wiring If branching the inter-adapter control wiring, the RS-232C cable is used to connect between the number of branches should be 16 or less. terminals CN4 of the large P.C.B. in S-DDC and Host (Branch length less than 1 m is not included in the Computer.
Page 131
Control of W-ECO MULTI SYSTEM 2. Optional Controller (S-DDC) Main P.C.B. for S-DDC NOTE * ln case of Host Computer (Program) has CD (Carrier Detect) function, RS switch is always ON 7 Connection to the outside equipments Fuse (1) Signal input for turn-off the all units. (Potential free normal open contact) <Inputting photo coupler>...
Page 132
Control of W-ECO MULTI SYSTEM 2. Optional Controller (AMY adapter) 7 How to install the AMY adapter (SHA-KC3500G) Hook the AMY adapter to the fixture 7 Accessories Accompanying parts Q’ty Accompanying parts Q’ty Fixture Screws for Nylon clamper (3 × L8) Screws (4 ×...
Page 133
Control of W-ECO MULTI SYSTEM 2. Optional Controller (AMY adapter) 7 Wiring diagram (2) Connecting control wires. Use two-core, 0.5 mm to 1.6 mm lead wires for AMY and inter-unit control wiring for AMY adapter both AMY control and inter-unit control wires. The should be wired as shown below.
Control of W-ECO MULTI SYSTEM 2. Optional Controller (AMY adapter) 7 Wiring procedure Main P.C.B. for AMY adapter ¶ Inter-unit control wire Inter-unit control wire is used to connect between the AMY adapter and the indoor or the outdoor unit. Connect the inter-unit control wire to the terminals 1 Fuse and 2 on the terminal plate TB1 of large P.C.B..
Page 135
Control of W-ECO MULTI SYSTEM 2. Optional Controller (AMY adapter) 7 Switch setting 7 Connection to the outside equipments (1) Signal input for turn-off the all units. (Potential free normal open contact) <Inputting photo coupler> Potential free contact Not defined. Address Test Mode: Keep these...
W-ECO MULTI SYSTEM Unit Specifications Contents 4. W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit .................. IV - 3 1-1. Specifications ..............................IV - 1-2. Major component specifications ........................IV - 11 1-3. Dimensional data ............................IV - 19 1-4. Refrigerant flow diagram ..........................IV - 22 1-5.
Page 137
W-ECO MULTI SYSTEM Unit Spesifications Contents 9. Floor-Standing Type (F Type) ............IV - 115 9-1. Specifications ..............................IV - 115 9-2. Major component specifications ........................IV - 119 9-3. Dimensional data ............................IV - 123 9-4. Noise criterion curves ............................ IV - 124 9-5.
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R407C) 1-1. Specifications Unit specifications (A) MODEL No. Outdoor Unit SPW-CR1503GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 45.0 50.0 BTU / h...
Page 139
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R407C) Unit specifications (B) MODEL No. Outdoor Unit SPW-CR1903GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 56.0 63.0 BTU / h 191,000 215,000 Air circulation (Hi)
Page 140
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R407C) Unit specifications (C) MODEL No. Outdoor Unit SPW-CR703GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 22.4 25.0 BTU / h 76,400 85,300 Air circulation (Hi)
Page 141
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R407C) Unit specifications (D) MODEL No. Outdoor Unit SPW-CR903GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 28.0 31.5 BTU / h 95,500 107,500 Air circulation (Hi)
Page 142
W-ECO MULTI SYSTEM Unit Specifications (For R22) 1. Outdoor Unit Unit specifications (E) MODEL No. Outdoor Unit SPW-C1503GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 45.0 50.0 BTU / h 154,000 171,000 Air circulation (Hi)
Page 143
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R22) Unit specifications (F) MODEL No. Outdoor Unit SPW-C1903GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 56.0 63.0 BTU / h 191,000 215,000 Air circulation (Hi)
Page 144
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R22) Unit specifications (G) MODEL No. Outdoor Unit SPW-C703GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 22.4 25.0 BTU / h 76,400 85,300 Air circulation (Hi)
Page 145
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R22) Unit specifications (H) MODEL No. Outdoor Unit SPW-C903GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Cooling Heating Capacity 28.0 31.5 BTU / h 95,500 107,500 Air circulation (Hi)
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R407C) 1-2. Major component specifications Outdoor Unit (A) MODEL No. SPW-CR1503GDYH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR1503GDYH8, CR - DYPTG...
Page 147
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R407C) Outdoor Unit (B) MODEL No. SPW-CR1903GDYH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR1503GDYH8, CR - DYPTG Control circuit fuse 250 VAC , 15 A Compressor PC (Power Control)
Page 148
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R407C) Outdoor Unit (C) MODEL No. SPW-CR703GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model …...
Page 149
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R407C) Outdoor Unit (D) MODEL No. SPW-CR903GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model …...
Page 150
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R22) Outdoor Unit (E) MODEL No. SPW-C1503GDYH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR1503GDYH8, CR - DYPTG Control circuit fuse 250 VAC , 15 A Compressor PC (Power Control)
Page 151
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R22) Outdoor Unit (F) MODEL No. SPW-C1903GDYH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR1503GDYH8, CR - DYPTG Control circuit fuse 250 VAC , 15 A Compressor PC (Power Control)
Page 152
W-ECO MULTI SYSTEM Unit Specifications 1. Outdoor Unit (For R22) Outdoor Unit (G) MODEL No. SPW-C703GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model …...
Page 153
W-ECO MULTI SYSTEM Unit Spesifications 1. Outdoor Unit (For R22) Outdoor Unit (H) MODEL No. SPW-C903GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model …...
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type 2-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-XR123GH56 / SPW-X123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase – 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000...
Page 161
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type Unit specifications (B) MODEL No. Indoor Unit SPW-XR183GH56 / SPW-X183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo)
Page 162
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type Unit specifications (C) MODEL No. Indoor Unit SPW-XR253GH56 / SPW-X253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 25,000 27,000 Air circulation (Hi / Me / Lo)
Page 163
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type Unit specifications (D) MODEL No. Indoor Unit SPW-XR363GH56 / SPW-X363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 10.6 11.4 BTU / h 36,000 39,000...
Page 164
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type Unit specifications (E) MODEL No. Indoor Unit SPW-XR483GH56 / SPW-X483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 14.0 16.0 BTU / h 47,800 54,600...
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type 2-2. Major component specifications Indoor unit (A) MODEL No. SPW-XR123GH56 SPW-X123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 …...
Page 166
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type Indoor unit (B) MODEL No. SPW-XR183GH56 SPW-X183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-41A5P …...
Page 167
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type Indoor unit (C) MODEL No. SPW-XR253GH56 SPW-X253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-41A5P …...
Page 168
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type Indoor unit (D) MODEL No. SPW-XR363GH56 SPW-X363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-61A3P…60 W...
Page 169
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type Indoor unit (E) MODEL No. SPW-XR483GH56 SPW-X483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Turbo (1 … ø 490) Fan motor Model…Nominal output SFG6X-61A3P…60 W...
W-ECO MULTI SYSTEM Unit Specifications 2. 4-Way Air Discharge Semi-concealed Type 2-3. Dimensional data Indoor unit : 12, 18, 25 Type 820 (Ceiling opening) 590 (Suspention bolt pitch) Air intake grille Air outlet Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line ø...
Page 171
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type Indoor unit : 36, 48 Type 820 (Ceiling opening) 590 (Suspention bolt pitch) Air intake grille Air outlet Refrigerant liquid line (ø9.52) Refrigerant gas line (ø19.05) Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole Suspension bolt mounting...
W-ECO MULTI SYSTEM Unit Spesifications 2. 4-Way Air Discharge Semi-concealed Type 2-5. Air throw distance chart Model: 12, 18, 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0276_X_I Model: 36, 48 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0277_X_I : LOUVER ANGLE 20˚ in Cooling mode : LOUVER ANGLE 60˚...
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type 3-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-SR93GH56 / SPW-S93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000...
Page 175
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Unit specifications (B) MODEL No. Indoor Unit SPW-SR123GH56 / SPW-S123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo)
Page 176
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Unit specifications (C) MODEL No. Indoor Unit SPW-SR183GH56 / SPW-S183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo)
Page 177
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Unit specifications (D) MODEL No. Indoor Unit SPW-SR253GH56 / SPW-S253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 25,000 27,000 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type 3-2. Major component specifications Indoor unit (A) MODEL No. SPW-SR93GH56 SPW-S93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 …...
Page 179
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Indoor unit (B) MODEL No. SPW-SR123GH56 SPW-S123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1…ø 190) Fan motor Model…Nominal output UF4X-31B3P ...
Page 180
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Indoor unit (C) MODEL No. SPW-SR183GH56 SPW-S183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 ... ø190) Fan motor Model…Nominal output KFG4X-51E3P ...
Page 181
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Indoor unit (D) MODEL No. SPW-SR253GH56 SPW-S253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 190) Fan motor Model…Nominal output KFG4X-51E3P ...
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type 3-3. Dimensional data Indoor unit : 9, 12 Type Refrigerant liquid line (ø 9.52) Refrigerant gas line (ø 12.7) Drain connection (25 A. O.D.32 mm) Power supply entry 0206_S_I TD831077 IV - 47...
Page 183
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type Indoor unit : 18, 25 Type Refrigerant liquid line (ø 9.52) (In case of 25 type, use the tube connector.) Refrigerant gas line (ø 15.88) Drain connection (25 A. O.D.32 mm) Power supply entry 0207_S_I TD831077...
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type 3-4. Noise criterion curves MODEL : SPW-SR93GH56 MODEL : SPW-SR123GH56 SPW-S93GH56 SPW-S123GH56 SOUND LEVEL : HIGH 32 dB(A), NC 29 SOUND LEVEL : HIGH 33 dB(A), NC 29 25 dB(A), NC 21 LOW 26 dB(A), NC 22 CONDITION : Center, Under the unit 1.5 m...
Page 185
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type MODEL : SPW-SR183GH56 MODEL : SPW-SR253GH56 SPW-S183GH56 SPW-S253GH56 SOUND LEVEL : HIGH 34 dB(A), NC 29 SOUND LEVEL : HIGH 37 dB(A), NC 33 27 dB(A), NC 24 30 dB(A), NC 29 CONDITION : Center, Under the unit 1.5 m CONDITION...
W-ECO MULTI SYSTEM Unit Specifications 3. 2-Way Air Discharge Semi-concealed Type 3-5. Air throw distance chart Model: 9, 12 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0282_S_I Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0283_S_I Model: 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0284_S_I...
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type 4-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-ASR93GH56 / SPW-AS93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000...
Page 188
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type Unit specifications (B) MODEL No. Indoor Unit SPW-ASR123GH56 / SPW-AS123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type 4-2. Major component specifications Indoor unit (A) MODEL No. SPW-ASR93GH56 SPW-AS93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 …...
Page 190
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type Indoor unit (B) MODEL No. SPW-ASR123GH56 SPW-AS123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 190) Fan motor Model…Nominal output UE6Q-21B3P …...
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type 4-3. Dimensional data Indoor unit : 9, 12 Type : Suspension bolt pitch : For ceiling opening 590** 483* Refrigerant liquid line (ø 9.52) Refrigerant gas line (ø 12.7) Drain connection (25 A, O.D.32 mm) Power supply entry Suspension holes (4-15 ×...
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type 4-4. Noise criterion curves MODEL : SPW-ASR93GH56 MODEL : SPW-ASR123GH56 SPW-AS93GH56 SPW-AS123GH56 SOUND LEVEL : HIGH 34 dB(A), NC 25 SOUND LEVEL : HIGH 38 dB(A), NC 32 30 dB(A), NC 22 31 dB(A), NC 25 CONDITION : Center, Under the unit 1.5 m...
W-ECO MULTI SYSTEM Unit Specifications 4. 1-Way Air Discharge Semi-concealed Type 4-5. Air throw distance chart Model: 9 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0287_AS_I Model: 12 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0288_AS_I 1: LOUVER ANGLE 10˚ in cooling mode 2: LOUVER ANGLE 20˚...
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type 5-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-KR93GH56 / SPW-K93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000 Air circulation (Hi / Me / Lo)
Page 195
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type Unit specifications (B) MODEL No. Indoor Unit SPW-KR123GH56 / SPW-K123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo) 630 / 490 / 430...
Page 196
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type Unit specifications (C) MODEL No. Indoor Unit SPW-KR183GH56 / SPW-K183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 17,000 20,000 Air circulation (Hi / Me / Lo) 800 / 660 / 520...
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type 5-2. Major component specifications Indoor unit (A) MODEL No. SPW-KR93GH56 SPW-K93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Cross-flow (1 … ø 81 / L 610) Fan motor Model…Nominal output UF2Q-21C5P …...
Page 198
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type Indoor unit (B) MODEL No. SPW- KR123GH56 SPW- K123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Cross-flow (1 … ø 81 / L 610) Fan motor Model…Nominal output UF2Q –...
Page 199
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type Indoor unit (C) MODEL No. SPW-KR183GH56 SPW-K183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Cross-flow (1 … ø 81/L610) Fan motor Model…Nominal output UF2Q-21B3P ...
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type 5-3. Dimensional data Indoor unit : 9, 12, 18 Type 0289_K_I TYPE OF COPPER TUBE TUBE OUTER DIAMETER NOTES NARROW 9.52 mm (3 / 8 inch) 9, 12, 18 type 12.7 mm (1 / 2 inch) 9, 12 type WIDE 15.88 mm (5 / 8 inch) 18 type TD831077...
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type 5-4. Noise criterion curves MODEL : SPW-KR93GH56 MODEL : SPW-KR123GH56 SPW-K93GH56 SPW-K123GH56 SOUND LEVEL : HIGH 38 dB(A), NC 33 SOUND LEVEL : HIGH 40 dB(A), NC 35 30 dB(A), NC 25 34 dB(A), NC 29 CONDITION : Distance 1 m, Under the unit 1 m...
W-ECO MULTI SYSTEM Unit Specifications 5. Wall Mounted Type 5-5. Air throw distance chart Model: 9 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 0293_K_I Model: 12 Type HORIZONTAL DISTANCE (m) 0294_K_I Model: 18 Type HORIZONTAL DISTANCE (m) 0295_K_I 1: LOUVER ANGLE 0˚ in cooling mode Condition Fan Speed : Hi 2: LOUVER ANGLE 30˚...
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type 6-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-TR183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo) 780 / 660 / 540...
Page 204
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Unit specifications (B) MODEL No. Indoor Unit SPW-TR253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 25,000 27,000 Air circulation (Hi / Me / Lo) 1,080 / 960 / 840 Moisture removal (High) Liters / h...
Page 205
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Unit specifications (C) MODEL No. Indoor Unit SPW-TR363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 10.6 11.4 BTU / h 36,000 39,000 Air circulation (Hi / Me / Lo) 1,680 / 1,410 / 1,200...
Page 206
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Unit specifications (D) MODEL No. Indoor Unit SPW-TR483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 14.0 16.0 BTU / h 47,800 54,600 Air circulation (Hi / Me / Lo) 1,920 / 1,680 / 1,320...
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type 6-2. Major component specifications Indoor unit (A) MODEL No. SPW-TR183GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3 … ø 130) Fan motor Model…Nominal output SR4X-31A3P …...
Page 208
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Indoor unit (B) MODEL No. SPW-TR253GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4 … ø 130) Fan motor Model…Nominal output SR4X-51A6P …...
Page 209
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Indoor unit (C) MODEL No. SPW-TR363GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4 … ø 150) Fan motor Model…Nominal output KFG4X-101C6P…100 W...
Page 210
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type Indoor unit (D) MODEL No. SPW-TR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4…ø150) Fan motor Model…Nominal output KFG4X-101C6P…100 W Source 220 - 230 - 240 V / 1 phase / 50 Hz...
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type 6-3. Dimensional data Indoor unit : 18, 25, 36, 48 Type Holes in the rear unit (View from front) Hole for wall-through piping (View from front) C (Suspension bolt hole pitch) Air outlet or more or more...
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type 6-4. Noise criterion curves MODEL : SPW-TR183GH56 MODEL : SPW-TR253GH56 SOUND LEVEL : HIGH 36 dB(A), NC 31 SOUND LEVEL : HIGH 39 dB(A), NC 34 30 dB(A), NC 23 34 dB(A), NC 26 CONDITION : Distance 1 m, Under the unit 1 m CONDITION...
W-ECO MULTI SYSTEM Unit Specifications 6. Ceiling Mounted Type 6-5. Air throw distance chart Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1224_T_I Model: 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1225_T_I Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1226_T_I Model: 48 Type...
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type 7-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-UR93GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity for Multi system (R22 and R407C) BTU / h 9,600 11,000...
Page 215
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Unit specifications (B) MODEL No. Indoor Unit SPW-UR123GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity for Multi system (R22 and R407C) BTU / h 12,000 14,000...
Page 216
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type Unit specifications (C) MODEL No. Indoor Unit SPW-UR183GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity for Multi system (R22 and R407C) BTU / h 19,000 21,000...
Page 217
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Unit specifications (D) MODEL No. Indoor Unit SPW-UR253GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity for Multi system (R22 and R407C) BTU / h 25,000 27,000...
Page 218
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type Unit specifications (E) MODEL No. Indoor Unit SPW-UR363GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 10.6 11.4 for Multi system (R22 and R407C) BTU / h 36,000 39,000...
Page 219
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Unit specifications (F) MODEL No. Indoor Unit SPW-UR483GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 14.0 16.0 for Multi system (R22 and R407C) BTU / h 47,800 54,600...
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type 7-2. Major component specifications Indoor unit (A) MODEL No. SPW-UR93GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 190) Fan motor Model…Nominal output KFG4X-51C3P …...
Page 221
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Indoor unit (B) MODEL No. SPW-UR123GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 190) Fan motor Model…Nominal output KFG4X-51C3P …...
Page 222
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type Indoor unit (C) MODEL No. SPW-UR183GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 190) Fan motor Model…Nominal output KFG4X-51C3P …...
Page 223
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Indoor unit (D) MODEL No. SPW-UR253GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 190) Fan motor Model…Nominal output KFC4X-71B5P …...
Page 224
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type Indoor unit (E) MODEL No. SPW-UR363GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3 … ø 190) Fan motor Model…Nominal output KFC4X-141A5P…160 W Source...
Page 225
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Indoor unit (F) MODEL No. SPW-UR483GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3 … ø 190) Fan motor Model…Nominal output KFC4X-141A5P…160 W Source...
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type 7-3. Dimensional data Indoor unit : 9, 12, 18 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (narrow tube) Refrigerant gas line 9.12: ø12.7, 18: ø15.88 (wide tube) Upper drain port (O.D.
Page 227
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type Indoor unit: 25 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (narrow tube) (Use the tube connector) Refrigerant gas line ø15.88 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
Page 228
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type Indoor unit: 36, 48 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (narrow tube) Refrigerant gas line ø19.05 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 26 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150)
Page 229
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type 7 Flange for the air intake duct (Field supply) : For Concealed Duct Type Thickness more than T1.2 mm 260 (O.D.) 1766_U_I (mm) 200 3 × 200P = 9, 12, 18 type 698 600 170 –...
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type 7-4. Noise criterion curves MODEL : SPW-UR93GHN56, UR123GHN56 MODEL : SPW-UR183GHN56 SOUND LEVEL : HIGH 29 dB(A), NC 20 / LOW 22 dB(A), NC 13 SOUND LEVEL : HIGH 30 dB(A), NC 23 / LOW 25 dB(A), NC 17 CONDITION : Under the unit 1.5 m CONDITION...
Page 231
W-ECO MULTI SYSTEM Unit Spesifications 7. Concealed Duct Type MODEL : SPW-UR363GHN56 MODEL : SPW-UR483GHN56 SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 SOUND LEVEL : HIGH 40 dB(A), NC 33 / LOW 33 dB(A), NC 25 CONDITION : Under the unit 1.5 m CONDITION...
W-ECO MULTI SYSTEM Unit Specifications 7. Concealed Duct Type 7-5. Increasing the fan speed If external static pressure is too great (due to long Electrical component box extension of ducts, for example), the air flow volume Booster cable may drop too low at each air outlet. This problem may Booster cable be solved by increasing the fan speed using the motor...
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-DR253GH56 / SPW-D253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 25,000...
Page 234
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Unit specifications (B) MODEL No. Indoor Unit SPW-DR363GH56 / SPW-D363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 10.6 11.4 BTU / h 36,000...
Page 235
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Unit specifications (C) MODEL No. Indoor Unit SPW-DR483GH56 / SPW-D483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 14.0 16.0 BTU / h 47,800...
Page 236
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Unit specifications (D) MODEL No. Indoor Unit SPW-DR763GH5 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 22.4 25.0 BTU / h 76,400 85,300 Air circulation (Hi / Me / Lo)
Page 237
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Unit specifications (E) MODEL No. Indoor Unit SPW-DR963GH5 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity 28.0 31.5 BTU / h 95,500 107,500 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-2. Major component specifications Indoor unit (A) MODEL No. SPW-DR253GH56 / SPW-D253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 …...
Page 239
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Indoor unit (B) MODEL No. SPW-DR363GH56 / SPW-D363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 220) Fan motor Model…Nominal output KFC4X-201B5P …...
Page 240
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Indoor unit (C) MODEL No. SPW-DR483GH56 / SPW-D483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 250) Fan motor Model…Nominal output KFC4Q-401A5P …...
Page 241
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Indoor unit (D) MODEL No. SPW-DR763GH5 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 220) Fan motor Model…Nominal output KFC4X-201B5P …...
Page 242
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Indoor unit (E) MODEL No. SPW-DR963GH5 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 250) Fan motor Model…Nominal output KFC4X-401B3P …...
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-3. Dimensional data Indoor unit : 25, 36, 48 Type 25, 36 type 48 type Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line (ø...
Page 244
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Indoor unit : 76, 96 Type Refrigerant liquid line ø12.7 (narrow tube) Refrigerant gas line 76: ø25.4, 96: ø28.6 Power supply outlet Drain port (OD 32 mm) Duct connection for suction Duct connection for dicharge 4 - 37 ×...
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-4. Noise criterion curves MODEL : SPW-DR363GH56 MODEL : SPW-DR253GH56 SPW-D253GH56 SPW-D363GH56 SOUND LEVEL : HIGH 44 dB(A), NC 38 SOUND LEVEL : HIGH 45 dB(A), NC 39 CONDITION : Under the unit 1.5 m CONDITION...
Page 246
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type MODEL : SPW-DR763GH56 MODEL : SPW-DR963GH56 SOUND LEVEL : HIGH 48 dB(A), NC 42 SOUND LEVEL : HIGH 51 dB(A), NC 43 CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m SOURCE...
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-5. R.A.P. valve kit ¶ Connect two units in parallel for each indoor unit. ¶ Attach the R.A.P. valve kit within 30 meters from the indoor unit. ¶ Secure the R.A.P. valve kit using hanging bolts, etc. ¶...
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type 8-6. Indoor fan performance How to Read the Diagram The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m /minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control. The name plate values are shown based on the “H”...
Page 249
W-ECO MULTI SYSTEM Unit Specifications 8. Concealed Duct High Static Pressure Type Increasing the Fan Speed (96 type only) If external static pressure is too great (due to long Electrical component box extension of ducts, for example), the air flow volume Booster cable may drop too low at each air outlet.
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) 9-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-FR93GH56 / SPW-F93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000 Air circulation (Hi / Me / Lo)
Page 251
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Unit specifications (B) MODEL No. Indoor Unit SPW-FR123GH56 / SPW-F123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo)
Page 252
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Unit specifications (C) MODEL No. Indoor Unit SPW-FR183GH56 / SPW-F183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo)
Page 253
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Unit specifications (D) MODEL No. Indoor Unit SPW-FR253GH56 / SPW-F253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 24,000 27,000 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) 9-2. Major component specifications Indoor unit (A) MODEL No. SPW-FR93GH56 SPW-F93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 …...
Page 255
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Indoor unit (B) MODEL No. SPW-FR123GH56 SPW-F123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 153) Fan motor Model…Nominal output KFT4Q-21B3P …...
Page 256
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Indoor unit (C) MODEL No. SPW-FR183GH56 SPW-F183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 153) Fan motor Model…Nominal output KFG4Q-61C3P …...
Page 257
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) Indoor unit (D) MODEL No. SPW-FR253GH56 SPW-F253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 153) Fan motor Model…Nominal output KFG4Q-61C3P …...
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) 9-3. Dimensional data Indoor unit : 9, 12, 18, 25 Type Size Narrow Wide tube tube Type 9, 12 1065 9.52 12.7 18,25 1380 9.52 15.88 26 15 Side panel Refrigerant tubing space for downward tubing Air outlet 25 R...
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) 9-4. Noise criterion curves MODEL : SPW-FR93GH56 MODEL : SPW-FR123GH56 SPW-F93GH56 SPW-F123GH56 SOUND LEVEL : HIGH 33 dB(A), NC 27 SOUND LEVEL : HIGH 39 dB(A), NC 33 28 dB(A), NC 23 29 dB(A), NC 23 CONDITION : In front of the unit 1 m, HEIGHT 1 m...
W-ECO MULTI SYSTEM Unit Specifications 9. Floor-Standing Type (F Type) 9-5. Air throw distance chart Model: 9 Type Model: 12 Type AIR OUTLET HEATING CEILING AIR OUTLET HEATING CEILING COOLING COOLING HEATING HEATING COOLING COOLING FLOOR FLOOR HORIZONTAL DISTANCE (m) HORIZONTAL DISTANCE (m) 0838_V_I 0839_V_I...
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) 10-1.Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-FMR93GH56 / SPW-FM93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000 Air circulation (Hi / Me / Lo)
Page 262
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Unit specifications (B) MODEL No. Indoor Unit SPW-FMR123GH56 / SPW-FM123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo)
Page 263
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Unit specifications (C) MODEL No. Indoor Unit SPW-FMR183GH56 / SPW-FM183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo)
Page 264
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Unit specifications (D) MODEL No. Indoor Unit SPW-FMR253GH56 / SPW-FM253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 24,000 27,000 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) 10-2. Major component specifications Indoor unit (A) MODEL No. SPW-FMR93GH56 SPW-FM93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 …...
Page 266
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Indoor unit (B) MODEL No. SPW-FMR123GH56 SPW-FM123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (1 … ø 153) Fan motor Model…Nominal output KFT4Q-21B3P …...
Page 267
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Indoor unit (C) MODEL No. SPW-FMR183GH56 SPW-FM183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 153) Fan motor Model…Nominal output KFG4Q-61C3P …...
Page 268
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) Indoor unit (D) MODEL No. SPW-FMR253GH56 SPW-FM253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (2 … ø 153) Fan motor Model…Nominal output KFG4Q-61C3P …...
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) 10-3. Dimensional data Indoor unit : 9, 12, 18, 25 Type Size Narrow Wide tube tube Type 9, 12 9.52 12.7 18,25 1173 1007 1002 9.52 15.88 Air outlet Internal dimension) Air inlet 0756_M_I...
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) 10-4. Noise criterion curves MODEL : SPW-FMR93GH56 MODEL : SPW-FMR123GH56 SPW-FM93GH56 SPW-FM123GH56 SOUND LEVEL : HIGH 33 dB(A), NC 27 SOUND LEVEL : HIGH 39 dB(A), NC 33 28 dB(A), NC 23 29 dB(A), NC 23 CONDITION : In front of the unit 1 m, HEIGHT 1 m...
W-ECO MULTI SYSTEM Unit Specifications 10. Concealed Floor-Standing Type (FM Type) 10-6. Indoor fan performance How to Read the Diagram The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m /minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control. The name plate values are shown based on the “H”...
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) 11-1. Specifications Unit specifications (A) MODEL No. Indoor Unit SPW-SLR93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 9,600 11,000...
Page 274
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Unit specifications (B) MODEL No. Indoor Unit SPW-SLR123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 12,000 14,000 Air circulation (Hi / Me / Lo)
Page 275
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Unit specifications (C) MODEL No. Indoor Unit SPW-SLR183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 19,000 21,000 Air circulation (Hi / Me / Lo)
Page 276
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Unit specifications (D) MODEL No. Indoor Unit SPW-SLR253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating Capacity BTU / h 25,000 27,000 Air circulation (Hi / Me / Lo)
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) 11-2. Major component specifications Indoor unit (A) MODEL No. SPW-SLR93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3) Fan motor...
Page 278
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Indoor unit (B) MODEL No. SPW-SLR123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3) Fan motor Model…Nominal output SR4X - 31A3P...
Page 279
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Indoor unit (C) MODEL No. SPW-SLR183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (3) Fan motor Model…Nominal output SR4X - 31A3P...
Page 280
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) Indoor unit (D) MODEL No. SPW-SLR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) Centrifugal (4) Fan motor Model…Nominal output SFG4X - 51B5P...
W-ECO MULTI SYSTEM Unit Specifications 11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type) 11-3. Dimensional data Indoor unit : 9, 12, 18, 25 Type 9, 12, 18 Type 1233 1193 1089 1003 25 Type 1430 1390 1286 1200 Suspension bolt pitch For ceiling opening Air intake grille Air outlet...
Test Run and Others Contents 5. Test Run and Others 1. Test Run .................... V - 2 1-1. Test run procedure ............................V - 2 1-2. Monitor and self-diagnostic function ....................... V - 4 1-3. Alarm messages on CCU (CR-DYPTG) ......................V - 6 2.
Test Run and Others 1. Test Run 1-1. Test run procedure Start Turn on RCU. ADR switch Multiple remote of sub-remote controller control? S006 Setting of CCU S004 & S005 NOTE in PC unit S002 & S003 *One of CN031 of all linked outdoor CN031 (open*) units should be short.
Page 286
Test Run and Others 1. Test Run ¶ Test run procedure in detail The following addresses will be set in EEPROM (IC8) on indoor P.C.B. after test run. (Data is not set when shipped from factory). Item Factory Setting data code setting data R.C.
Test Run and Others 1. Test Run 1-2. Monitor and self-diagnostic function 7 Monitor function for CCU (CR-DYPTG) in PC unit By selecting the Item SW (S7) and Select SW (S8), the LED will display all the necessary information to be monitored. The monitored information stored in memory can be deleted by turning off the power supply.
Page 288
Test Run and Others 1. Test Run ITEM SELECT Message displayed SW (S7) SW (S8) Item RUN / ALARM LED MESSAGE LED RUN / ALARM LED Display of connected Vertical LED : Lights up starting from 1 in sequence by display does not affect indoor unit pressing the Select switch each time...
Test Run and Others 1. Test Run 1-3. Alarm messages on CCU (CR-DYPTG) ∗ During normal operation, either “OUTDOOR” or “CB” alarm lamp on CCU lights up with alarm display of LED1-8 (red). ∗ In case either “OUTDOOR” or “CB” alarm lamp lights up during automatic address operation, turn the “ITEM” switch to “4”...
Page 290
Test Run and Others 1. Test Run Remote LED (red) controller Alarm message display ∗ Overload current ∗ Lock current ∗ Current is not detected when compressor is ON PC comp. CT detection current O O O O Current is detected when compressor is OFF ∗...
Page 291
Test Run and Others 1. Test Run 7 Alarm messages on the outdoor P.C.B. When the outdoor alarm LED (yellow) is OFF and the alarm display LED (red) lamps blink Operation thermostat OFF, with no alarm display on the remote controller. When the outdoor alarm LED (yellow) is ON and the alarm display LED (red) lamps light up An alarm message is also displayed on the remote controller.
Page 292
Test Run and Others 1. Test Run Outdoor unit Remote LED (red) controller Alarm message PC unit AD unit display ∗ Overload current Overload current ∗ Lock current Lock current ∗ SC comp. CT detection O O O Current is not detected when Current is not detected current compressor is ON...
Test Run and Others 2. Electrical Work 2 -1. Electrical wiring ¶ Do not mistake the polarities of the wiring for group control and central control. ¶ Take the power supply for indoor units separately in units of each outdoor unit. 7 Cautions on electrical work ¶...
Test Run and Others 2. Electrical Work ¶ Engineering method 2-2. Noise countermeasures of control wiring 1. Ground the shield on both sides (Fig. 2-1) 2. Install the unit 3 m away from any nearby high 7 Signal line wiring between micro computer frequency equipment.
Test Run and Others 3. Installation Standards 3-1. Method of gas leak inspection after completing the tubing 1. Procedure Connect the indoor unit, tubing, and outdoor unit, and check for gas leakage according to the following procedure (also check the service valve and the sealing of spindle). Pressurize nitrogen gas Check for pressure Refrigerant tubing work...
Test Run and Others 3. Installation Standards 3-2. Check of density limit Do not install the indoor unit NOTE 2 : The standards for minimum room volume to the place, such as a are as follows. basement, etc. where No partition (shaded portion) refrigerant can stay, since refrigerant is heavier than air.
Test Run and Others 3. Installation Standards 3-3. Precautions for new refrigerant installation 1. Care regarding piping 1-1. There is no need to change piping and tube wall thickness. Use refrigerant pipes of the same wall thickness as R22. Unit: mm Type Outer diameter 6.35...
Test Run and Others 3. Installation Standards 3-4. New refrigerant R407C cannot be used for existing models 1. Compressor specs are different. When refilling the R22 compressor with R407C, durability will significantly decrease since some of the materials used for compressor parts are different. 2.
Processes and Functions 1. Compressor Control 1-1. Compressor capacity control (1) Outdoor unit operation control ¶ The compressor capacity is calculated by the C.C.U. based on the operation capacities of the indoor units and the difference between the temperature setting and room temperature. This is designated as the C.C.U. target capacity, and this is assigned to each outdoor unit as the outdoor unit target capacity.
Processes and Functions 2. Protection Controls ¶ If the C.C.U. target capacity decreases, the C.C.U. target capacity does not increase for one minute. ¶ If the outdoor unit capacity decreases, the capacity does not increase for one minute. However, the case in (6) under "1-1.
Page 302
Processes and Functions 2. Protection Controls (3) Coil temperature control 1 Evaporation temperature control The lowest of the E1, E2, and E3 temperatures of all indoor units whose cooling thermostat is on is designated as the minimum evaporation temperature (Te), and control is performed as shown in the table 7. This control is performed every 30 seconds.
Processes and Functions 3. Fan Control (1) Outdoor fan mode Table 10 Table 11 [PC unit] [AD unit] Mode Fan No. 1 Fan No. 2 Mode High High – High Medium – Medium Medium High Medium Medium High Stop Stop Medium Stop Stop...
Processes and Functions 5. Solenoid Valve Control ¶ In solenoid valve control, in addition to the conditions shown below, multiple valves may be controlled at the same time. This is performed according to the respective control items. (1) Liquid valve control (LIVP, LIVA, LIVS) To properly control the discharge temperature, control is performed on a small amount of liquid refrigerant bypass- ing to the suction pipe.
Processes and Functions 5. Solenoid Valve Control (8) PC oil valve control (OILP), SC oil valve control (OILS) There is no oil sensor in the AC compressor due to cross oil control. As a result, no oil valve is attached. Oil is constantly returning to the AC compressor by passing through a capillary tube.
Processes and Functions 6. Hot Gas Defrosting Control 6-2. Defrosting operation conditions (1) Defrosting operation is performed after at least 35 minutes of total operation during heating operation. * Even in outdoor units where a total operation time of 35 minutes has not elapsed, defrosting operation will be performed if other outdoor units satisfying the conditions above start defrosting operation.
Processes and Functions 9. Inter-Refrigerant System Oil Recovery Control ¶ Control is performed for recovering the oil accumulated in the indoor unit, refrigerant pipes, or other locations in the system. (maximum of two minutes) Control description ¶ If the oil does not return to the original level even after the oil level reaches 0 and operation is performed for a set time, the thermostat for the outdoor unit is turned off.
Processes and Functions 12. Backup Operation ¶ Types of backup operation (1) Electrically disconnecting a unit Disconnect the inter-control unit wire from the faulty outdoor unit, and set the number of C.C.U. AD units to the number of outdoor units that are connected electrically minus one. Close the service valve of the faulty unit.
Processes and Functions 13. Room Temperature Control The thermostat is switched on/off by ∆T as follows. ∆T = (Room temperature) – (Set temperature) Remote control sensor Room temperature = remote control sensor detection temperature Body sensor Room temperature = (Body sensor detection temperature) – (Air-intake shift temperature*) * Shift temperature (valid only for heating) In heating mode, a temperature difference occurs between the upper part and lower part of a room.
Processes and Functions 15. Heating Preparations (1) After thermo.-on, until the set fan speed is reached, cool air is output (emanates) from this begin- ning heating operation and the indoor fan speed is controlled as shown below to prevent cold draft. ¶...
Processes and Functions 16. Dehumidifying Control A: Normal cooling operation Room temperature (°C) B: Thermo-on • • • • • : Low fan speed Thermo-off • • • • • : Very low fan speed Remote control temperature setting 1268_M_I 17.
Processes and Functions 18. Auto-flap Control 18-1. X, S, T Type The auto-flap controls the air flow to one of the five vertical levels. X type (4-way), S type (2-way) T type Auto-flap 20° 60° 40° Cooling F1~F3 Heating F1~F5 1267_M_I Flap position Operation mode...
Processes and Functions 19. Drain Pump Control (Does not include K, T, D, F, FM Type) (1) Drain pump control turns ON when the compressor is activated in cooling operation. (2) When the compressor turns OFF due to freeze prevention control, drain pump turns ON for 20 minutes. (3) Drain pump control turns ON when the floating switch is activated.
Processes and Functions 21. Discharge Temperature Control (Only for U, D Type) ¶ If the range shown below is continuously detected for 6 minutes, the unit will thermo-off operation is initiated. Room temp. (deg) A: Thermo-off range in heating B: Thermo-off range in cooling (drying) Discharge Set temp.
Replacement of Main Units Contents 7. Replacement of Main Units 1. Compressors ................VII - 2 1-1. Judging whether a compressor needs to be replaced .................. VII - 2 1-2. Procedure for Replacing one faulty Compressor ..................VII - 3 1-3.
Replacement of Main Units 1. Compressors Compressor trouble can generally be grouped under the following categories: Mechanical trouble → (A) Compressor lock-up (B) Trouble in boosting pressure (C) Abnormal noises → (A) Winding burn-out Electrical trouble (B) Broken or disconnected wires (C) Defective insulation (D) Ground faults Troubleshooting consists in pinpointing the trouble from the winding resistance (which differs depending on the...
Replacement of Main Units 1. Compressors 1-2. Procedure for Replacing one faulty Compressor Start Replace one compressor Turn off the faulty outdoor unit (PC unit) in PC unit Close the valves (three) of the faulty outdoor unit (balance, liquid, and gas pipe valves) Run the buck up operation Change the AD unit quantity settings of the C.C.U.
Page 319
Replacement of Main Units 1. Compressors (1) Refrigerant Recovery and Oil Recovery of the Faulty Unit (Always use the refrigerant recovery device) Dirty oil and refrigerant from the faulty unit must not be recovered in another unit. Use the following procedure to correctly perform refrigerant and oil recovery.
Replacement of Main Units 1. Compressors 1-3. PC unit (1) Replacing the power control (PC) compressor (Ref. Fig. 1) [Removal] Remove the front panel at the front. Remove the sound-proofing material which is wrapped around the compressor. Remove the cap over the compressor terminal section, and disconnect the power and internal terminals. (Do this in two places at the left and right.) Remove the crankcase heater.
Page 321
Replacement of Main Units 1. Compressors Close valve V9 and open valve V6 and inspect for leaks. (Keep the pressure within the 1.27 to 1.47 MPa (13-15 kg/cm range in order to protect the low-pressure switch.) (Ref. Fig. A) Under no circumstances, do not exceed pressure 1.47 MPa (15 kg/cm ).
Page 322
Replacement of Main Units 1. Compressors Braze with copper. Close valve V9 and open valve V6 and inspect for leaks. (Keep the pressure within the 1.27 to 1.47 MPa (13-15 kg/cm range in order to protect the low-pressure switch.) (Ref. Fig. A) Under no circumstances do not exceed pressure 1.47 MPa (15 kg/cm NOTE When the refrigerant has been recovered in the PC unit, inspect for leaks using a refrigerant gas...
Page 323
Replacement of Main Units 1. Compressors 11. Proceed as instructed below to check whether any oil has accumulated in the suction pipe. ¶ Loosen the lower flare part of the oil sensor, and drain off the oil until no more comes out. (Be absolutely sure to provide a pan large enough to collect about a liter of oil.) ¶...
Replacement of Main Units 1. Compressors 1-4. AD unit (1) Replacing the compressor (Ref. Fig. 5, 6) [Removal] Remove the front panel. Remove the electrical parts box. Top panel Remove the part of the compressor cover. ¶ Disconnect the wires bundled together by the clamper.
Page 325
Replacement of Main Units 1. Compressors [Installation] Prepare to install the compressor. ¶ Remove the crankcase heater. ¶ Remove the compressor. Nuts with washers ¶ Install the new compressor. Install it in the same status that the old compressor was originally in. ¶...
Page 326
Replacement of Main Units 1. Compressors (2) Air Purging with a Vacuum Pump, refilling the oil/refrigerant [Measuring the amount of oil] Measure the amount of oil in the compressor which has been removed and determine whether more oil needs to be added.
Replacement of Main Units 1. Compressors 1-5. Replacing the Compressors (Three) of the PC Unit * Never attempt to recover the refrigerant or oil of the faulty unit (PC unit) in another unit (AD unit). See the flowchart in “1-1. Judging whether a compressor needs to be replaced” and Fig. A (P19). Start Turn off the faulty outdoor unit (PC unit) Close the valves (three) of the faulty outdoor unit (balance, liquid, and gas pipe valves)
Page 328
Replacement of Main Units 1. Compressors (1) Vacuum and Oil and Refrigerant Injection [Measurement of oil amount] Measure the oil amount in the faulty compressor and the oil amount recovered in the oil separator to determine the amount of new oil to be added. Total amount of Amount of oil to be added recovered oil (l) (two...
Page 329
Replacement of Main Units 1. Compressors ¶ When a ball valve is not installed at the outdoor unit side The refrigerant inside all indoor units and the pipes between all units must be pumped down to the outdoor unit side. The pumping down capacity of this outdoor unit is approximately 10 kg in this system.
Replacement of Main Units 1. Compressors 1-6. Procedure for Replacing All Compressors in the Same System Always recover all the refrigerant and oil in the same system without releasing them into the open air. Perform opera- tions according to the flowchart below. Never reuse the recovered refrigerant and oil. Start Turn off each outdoor unit Short-circuit the AP service pins on the PCBs of each outdoor unit, and then turn on each outdoor unit (NOTE 1)
Page 331
Replacement of Main Units 1. Compressors (1) Injection of Oil and Refrigerant [Oil injection] Inject the oil amount below into each model from the oil removal service port of each model. 2.4 l [Refrigerant injection] Find the refrigerant injection amount using the formula below. Total default refrigerant Additional refrigerant Refrigerant...
Replacement of Main Units 2. Indoor Units 2-1. Refrigerant recovery when a fault occurs in the indoor unit The procedure for refrigerant recovery when replacing or repairing an indoor unit due to a faulty refrigerant recovery circuit or other cause is shown below. Be sure to perform this procedure correctly. When a fault has occurred not requiring Start Check whether the...
Replacement of Main Units 2. Indoor Units 2-2. Refrigerant Recovery Operation When a ball valve is installed) Cooling operation Ball valve (option) Gas pipe (wide pipe) Service port Indoor unit (ø6.35 flare with push-pin) Outdoor unit Valve (field supply ) Liquid pipe (narrow pipe) 1877_M_I...
Page 334
Replacement of Main Units 2. Indoor Units 7 7 7 7 7 Refrigerant recovery and oil recovery PC unit AD unit Gauge Closed Service Open port Half open Closed Closed Open Open Closed Gauge Dry core Dry core Gauge separator tank Ball valve Balance tube...
Page 335
Replacement of Main Units 2. Indoor Units 7 7 7 7 7 When a ball valve is installed PC unit AD unit Gauge Service Open port Open Open Open Open Open Closed Gauge Dry core Dry core Gauge Ball valve Balance tube Wide tube Narrow tube...
Page 336
Replacement of Main Units 2. Indoor Units 7 7 7 7 7 When a ball valve is not installed PC unit AD unit Gauge Service Open Open Open Open port Open Open Closed Closed Closed Closed Gauge Dry core Dry core Gauge Balance tube Wide tube...
Page 374
Appendix 1. P.C.B. illustrations Outdoor unit control P.C.B. (CR-CR703GDCH8) JP006 LED : MESSAGE LAMPS : Power supply voltage < protection ( 260V) cancel S003 : Model select SW JP005 S002 CN034 (YEL) : TP : Power supply voltage < protection ( 160V) cancel CN033 (RED) : CP CN032 (WHT) : OAC CN031 (WHT) : RPSW...
Page 375
Appendix 1. P.C.B. illustrations Outdoor unit control P.C.B. (CR-CR1503GDYH8) < = J005 : Power supply voltage protection ( 160V) cancel CN046 (BLK) : 49F / 49C < = J006 : Power supply voltage protection ( 260V) cancel CN045 (BLU) : 63PH3 CN050 (RED) : 52C3 / 52C2 CN044 (RED) : 63PH2...
Page 376
Appendix 1. P.C.B. illustrations Outdoor unit control CCU (Command control unit: CR-DYPTG) S007 (BLK) : ITEM CN050 (GRY) : 02 ALARM CN010 (WHT) : AC S008 : SELECT LED : MESSAGE LAMPS CN080 (RED) : AIR TEMP JP021 S030 JP020 S009 How many AD units CN021 (WHT)
Page 377
• The specifications, designs, and information in this brochure are subject to change without notice. SANYO Electric Air Conditioning Co., Ltd. Tochigi, Japan G0900 G 1000 Printed in Japan...