Technical features Switch Actuator 16A, 1 switch The one-channel 16A Switch Actuator one switch is a flash-mounted device for the ABB's Mylos Building Automation system. On the rear side, the device has an exchange output contact (NA/NC) that can be configured for the control of different kinds of loads.
MYLOS Building Automation Technical features ® Device type Application program Maximum number Maximum number of Maximum number of of communication group addresses associations objects 2CSYK1102x Switching 1c 16A/1.0 1 interr. 1.1.2 Connection diagram 3 2 1 – – 4 Technical features | MYLOS Building Automation ®...
Technical features ® Switch Actuator 16A, 2 switches The one-channel 16A Switch Actuator two switches is a flash-mounted device for the ABB's Mylos Building Automation system. On the rear side, the device has an exchange output contact (NA/NC) that can be configured for the control of different kinds of loads.
MYLOS Building Automation Technical features ® Device type Application program Maximum number Maximum number of Maximum number of of communication group addresses associations objects 2CSYK1103x Switching 1c 16A/1.0 2 switches 1.2.2 Connection diagram 3 2 1 – – 6 Technical features | MYLOS Building Automation ®...
Switch Actuator 8A, 2 switches The 2-channel 8A Switch Actuator with two switches is a flash-mounted device for the ABB's Mylos Building Automation system. On the rear side, the device has a bus connection and two output contacts (NA) that can be configured for the control of different kinds of loads.
MYLOS Building Automation Technical features ® Device type Application program Maximum number Maximum number of Maximum number of of communication group addresses associations objects 2CSYK1106x Switching 2c 8A/1.0 2 switches 1.3.2 Connection diagram – – 8 Technical features | MYLOS Building Automation ®...
Page 9
MYLOS Building Automation Technical features ® Supplied state The device is supplied with the physical address 1.0.1. The application program is preloaded. It is therefore only necessary to load group addresses and parameters during commissioning. However, the complete application program can be reloaded if required.
MYLOS Building Automation Commissioning ® Commissioning The main functions of the 2CSYK110xx Switch Actuators are described in this section. The 16A Switch Actuator parametrisation is performed via the Engineering Tool ETS Software application program. For the parametrisation you need a pc desktop or a laptop with ETS and connection to the KNX system (obtainable for example by means of RS232, USB or IP Interface).
Page 11
MYLOS Building Automation Commissioning ® Options: - Unchanged contact - Open contact - Closed contact Switching object value upon bus voltage restoration With this parameter you can affect the output upon bus voltage restoration using the "Switching" object value. The "Switching" object can be written with '0' or '1' when bus voltage is restored. The contact position is determined again and the device parametrisation function is set.
MYLOS Building Automation Commissioning ® Function Output contact reaction With this parameter you can determine whether the output works as a "Normally closed contact" or as a "Normally open contact" Options: - Normally open contact - Normally closed contact Enabling time functions: delay and stairlights This parameter enables the following time functions: Delay upon switching on and switching off, stairlights.
Page 13
MYLOS Building Automation Commissioning ® “Enable scene function (8 Bit)” parameter The “8-Bit scene” object is enabled through this parameter. Options: - no - yes The scene parametrisation for the X output is implemented in the "X: Scene” parameter window, which is enabled with the option “yes”.
Page 14
MYLOS Building Automation Commissioning ® Forced operation upon bus voltage restoration This parameter is visible only if the forced operation is activated. Depending on whether the forced operation object is a 1 bit or 2 bit object, two different types of programming are available: Options for 1 bit: - inactive...
MYLOS Building Automation Commissioning ® Time - Stairlights "Time function" parameter This parameter defines the type of output time function. Options: - Stairlight function - Delay ON/OFF - Flashing "Stairlight function" selection The stairlight function is activated via the switch on the “Switching” communication object telegram of X output. The communication object value can be programmed.
Page 16
MYLOS Building Automation Commissioning ® Options: Minutes - ... - ... - 1.000 Seconds - ... - 59 If the pre-warning time is different from "0", the stairlight time is extended with the pre-warning time. "Stairlight time increases by means of multiple ON" parameter If during stairlight time a further ON telegram is received, the remaining stairlight time can be extended with an additional time.
Page 17
MYLOS Building Automation Commissioning ® "Pre-warning before the stairlight end" parameter Before stairlight time elapses, the user can be warned that the lights are about to be turned off. If the pre-warning time is different from "0", the stairlight time is extended with the pre-warning time. The pre-warning time is not modified by the "increasing"...
MYLOS Building Automation Commissioning ® Time - On/off delay “Delayed ON: Min. (0...65.535)” parameter Here you set the time in minutes by which the switching on command is delayed. The time can be entered in minutes and in seconds (see the following parameter). Options: - ...
Page 19
MYLOS Building Automation Commissioning ® "Delayed OFF: Sec. (0...59)” parameter Here you set the time in seconds by which the switching off is delayed after a switching off command. The time can be entered in minutes and in seconds (see the previous parameter). Options: - ...
MYLOS Building Automation Commissioning ® Scenes The scene function is enabled in the "Function" parameter window. Scene values can be set (stored) over the bus. In the "General" parameter window you can determine that the values set in the ETS are transferred in the Switch Actuator during download. In this mode the values stored in the terminal are overwritten and lost.
MYLOS Building Automation Commissioning ® Logic function For each output the logic function makes up to two logic objects available, that are logically connected to the “Switching” communication object. The parameter window is enabled in “Function”. When receiving an object value, the logic function is always recalculated. First of all the “Logic gate 1” object is evaluated with the “Switching”...
Page 22
MYLOS Building Automation Commissioning ® “Invert result” parameter This parameter is visible only if a logic function has been selected. The logic operation result can be inverted using the "Yes" setting. The “no” setting does not invert the result. Options: - no - yes “‘Logic gate x’...
MYLOS Building Automation Commissioning ® Rocker switch 1/2 2.7.1 Switching Rocker switch Upper Rocker switch push-button operation It defines the operating mode if an upper or lower Rocker switch is pressed. Cyclic sending This parameter allows you to determine in which cases the cyclic sending should begin (if different from "no"). Base for cyclic repetition (if “Cyclic Sending”...
MYLOS Building Automation Commissioning ® 2.7.2 Rocker switch 2 switching objects Upper Rocker switch operation It defines the operating mode if the upper rocker switch is pressed. Upper push-button cyclic sending This parameter allows you to determine in which cases the cyclic sending should begin (if different from "no"). Base for cyclic repetition: upper push-button (if “Cyclic Sending”...
MYLOS Building Automation Commissioning ® LED operating mode The LEDs can remain always on or always off, they can be controlled by communication objects ("Show communication object value"), follow the rocker switch direct value ("Show rocker switch object value) or inverted value ("Show rocker switch object inverted value").
MYLOS Building Automation Commissioning ® Shutter rocker switch 2.8.1 Rocker switch - Standard Shutter functionality With this parameter it is possible to choose between the following shutter control modes: - Rocker switch - Standard; - Rocker switch – Movement. Rocker switch reaction to short pressure Upper – Lower Rocker switch It determines device reaction after a short pressure on the upper and lower rocker switch.
MYLOS Building Automation Commissioning ® 2.8.2 Rocker switch - Movement Shutter functionality With this parameter it is possible to choose between the following shutter control modes: - Rocker switch - Standard; - Rocker switch – Movement. Rocker switch reaction to pressure Upper – Lower Rocker switch It determines device reaction after a pressure on the upper and lower rocker switch.
MYLOS Building Automation Commissioning ® Scene rocker switch Reaction to short pressure After a short pressure the device will respond recalling a scene ("Recall scene") or not ("No reaction"). Store scene This parameter determines the way in which the current scene storage begins and which function the "Store scene" communication object has.
MYLOS Building Automation Commissioning ® 2.9.1 Scene Actuator unit A/B/C/D/E check via It is possible to choose only one type of 1 bit datum. Actuator unit A/B/C/D/E value It associates the corresponding actuator unit with a 1 bit value (ON/OFF). MYLOS Building Automation | Commissioning 29 ®...
MYLOS Building Automation Commissioning ® 2.10 8 bit scene rocker switch Reaction to short pressure After a short pressure the device will respond recalling a scene ("Recall scene") or not ("No reaction"). Upper rocker switch scene This parameter allows you to choose which scene should be recalled with the short pressure of the upper rocker switch or which scene the new value should be associated with after a storage request.
Page 31
MYLOS Building Automation Commissioning ® Long pressure: Base Long pressure: Multiplier [0…255] (if “In case of long pressure” or if “in case of long pressure (if object value = 1)”) These two parameters allow you to determine the time that is sufficient to consider a pressure as a long pressure. Time interval is calculated as follows: Period for long pressure = Base * Multiplier.
MYLOS Building Automation Operation of communication objects ® Operation of communication objects Function Object name Type of datum Flags Switching Output A 1 bit (EIS 1) DPT 1.001 C, W Switching Output B 1 bit (EIS 1) DPT 1.001 C, W This object is used to switch an output ON/OFF.
Page 33
MYLOS Building Automation Operation of communication objects ® This object is visible if in the "Function" parameter window the "Switching status in forced operation" has been selected as 2 bit object. The output can be controlled forcedly using this object (for example an upper level control). The object value defines the contact forced position.
Page 34
MYLOS Building Automation Operation of communication objects ® This object will be visible if the time function in the “X: Time” parameter window and a pre-warning object via the “Pre-warning before stairlight end” parameter are selected. The object value is programmable and gives a pre- warning before the stairlights are turned off.
MYLOS Building Automation Operation of communication objects ® Rocker switch 1/2 3.1.1 Switching rocker switch Function Object name Type of datum Flags Disabling Rocker switch 1 1 bit DPT_Enable C,W,T Disabling Rocker switch 2 1 bit DPT_Enable C,W,T,U The channel circuitry can be blocked or enabled using the communication object. A blocked channel behaves as if there was no input signal.
MYLOS Building Automation Operation of communication objects ® Upper rocker switch Rocker switch 1 1 bit DPT_Switch C,W,T Switching Upper rocker switch Rocker switch 2 1 bit DPT_Switch C,W,T Switching Telegram value: “0” OFF “1” ON According to parameter setting, this communication object can be switched by the ON, OFF or Switching input drive.
MYLOS Building Automation Operation of communication objects ® According to parameter setting, this communication object can be switched by the ON, OFF or Switching input drive. With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure that the communication object can be written from the outside.
MYLOS Building Automation Operation of communication objects ® The “Disabling Led” communication object makes it possible to enable (1) the LED so as that it switches on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a continuous switching off status.
MYLOS Building Automation Operation of communication objects ® 3.1.6 8 bit scene rocker switch Function Object name Type of datum Flags Disabling Rocker switch 1 1 bit DPT_Enable Disabling Rocker switch 2 1 bit DPT_Enable The channel circuitry can be blocked or enabled using the communication object. A blocked channel behaves as if there was no input signal.
MYLOS Building Automation Operation of communication objects ® 3.1.7 Direct LED management Function Object name Type of datum Flags Upper LED Rocker switch 1 1 bit DPT_Switch Upper LED Rocker switch 2 1 bit DPT_Switch Through these communication objects it is possible to control the upper LED status directly over the bus. Send a telegram containing the value 1 to switch them on, or value 0 to switch them off.
MYLOS Building Automation Table of 8 bit scene telegram codes ® Table of 8 bit scene telegram codes Scene number Scene number MYLOS Building Automation | Table of 8 bit scene telegram codes 41 ®...
Page 42
Wiring accessories, Home & Building automation without prior notice. Viale dell’Industria, 18 Copyright 2012 ABB. All rights reserved. 20010 Vittuone (MI), Italy Tel.: +39 02 9034 1 Fax: +39 02 9034 7609 www.abb.it/mylos...