Duct-Free Split Systems provide industry leading technical support during installation and LG HVAC systems offer a range of solutions that are cost efficient, commissioning. LG offers a variety of classes designed for installers quiet and attractive. Duct-Free Split systems are “split” into indoor...
TABLE OF CONTENTS INTRODUCTION ..................5 PERFORMANCE DATA ................ 27 Cooling Capacity ................28 ARCHITECTURAL APPEAL ..............6 Heating Capacity ................30 Maximum Heating Capacity ............... 32 PRODUCT FEATURES AND BENEFITS ..........8 Air Flow and Temperature Graphs ............. 34 UNIT NOMENCLATURE .................
Single Zone Art Cool Benefits of Single Zone Mirror Wall-Mounted Art Cool Mirror Wall-Mounted System Systems Choosing an LG Single-Zone Art Cool • Available in 9,000 - 24,000 Btu/h Mirror Wall-Mounted product provides a system designer an edge to engineer • Inverter technology a system with individual control, and design flexibility with advanced controls.
PRODUCT DATA “Product Features and Benefits” on page 8 “Unit Nomenclature” on page 9 “General Data” on page 10 “Electrical Data” on page 12 “Outdoor Unit Dimensions” on page 14 “Indoor Unit Dimensions” on page 16 “Acoustic Data” on page 18 “Refrigerant Flow Diagram”...
Operating Range mote a quiet, comfortable environment, the Single zone systems have a nominal capac- LG single zone system indoor units operate ity range of 3/4 to 2 tons (depending on at sound levels as low as 23 dB(A) (19dB(A) outdoor/indoor units).
UNIT NOMENCLATURE Single Zone Wall Mount Indoor and Outdoor Units Family LA= Art Cool Premier / Gallery / Mirror LS= High Efficiency Wall Mount / Standard / Mega Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit Nominal Capacity (Nominal cooling capacity in Btu/h) 090/091 = 9,000...
GENERAL DATA Art Cool Mirror Pairing Table The following table shows the available outdoor and indoor units, along with the factory provided controller. Table 1: Single Zone Art Cool Mirror Pairing Table Outdoor Unit Model Indoor Unit Model Controller LSU090HSV4 LAN090HSV4 AKB73835317 LSU120HSV4...
Page 11
GENERAL DATA Table 2: LA090HSV4 LA120HSV4 LA180HSV4 LA240HSV3 System Model Number (IDU/ODU) (LAN090HSV4/ (LAN120HSV4/ (LAN180HSV4/ (LAN240HSV3/ LSU090HSV4) LSU120HSV4) LSU180HSV4) LAU240HSV3) Cooling Capacity (Min/Rated/Max) (Btu/h) 1,023 ~ 9,000 ~ 12,625 1,023 ~ 11,200 ~ 13,785 3,070 ~ 18,200 ~ 29,515 3,070 ~ 22,000 ~ 30,030...
Dry contact Central control (LGAP) PI 485 Zone control CTIE Electro thermostat Wi-Fi Module (Option) Water level sensor connection (for optional AG-9300-LG) Wind baffle kit ZLABGP01A ZLABGP01A ZLABGP02A ZLABGP02A Primary washable filters. • When Dry Contact Mode active, Wi-Fi Function can not be used.
INDOOR UNIT DIMENSIONS LAN090HSV4, LAN120HSV4 8-1/16 34-13/16 1-3/4 1-3/4 2-3/16 15/16 2-5/16 6-5/16 Place a level on raised tab Unit Outline 17-3/8 17-3/8 Return Air Grille for piping and cables Ø2-9/16 Ø2-9/16 Left rear piping Right rear piping 3-11/16 5-1/8 6-15/16 8-1/2 [Unit : Inch]...
OUTDOOR UNIT ACOUSTIC DATA • Measurements are taken 3.28 ft away from the front of the unit. Figure 1: Outdoor Unit Sound Levels • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under Center of ISO Standard 3745.
Page 19
INDOOR UNIT ACOUSTIC DATA Figure 3: Indoor Unit Sound Levels • Measurements are taken 3.28 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. •...
REFRIGERANT FLOW DIAGRAMS LSU/LAN090HSV4, LSU/LAN120HSV4 Indoor Unit Outdoor Unit FIELD PIPI N G 2-Way Valve (Ø 1/ 4” Copper Tubing) Liquid Side He at Heat Exchanger Exchanger (Evaporator) (Condenser) Reve rsing 3- Wa y Valve FIELD PIPI N G Valve (Ø...
REFRIGERANT FLOW DIAGRAMS LSU/LAN180HSV4, LAU/LAN240HSV3 Indoor Unit Outdoor Unit FIELD PIPIN G 2-Way Valve (Ø 3/ 8” Copper Tubing) Liqui d Side He at Heat Exchanger Exchanger (Ev aporator) (Condenser) Reve rsing 3- Way Valve FIEL D PIPI N G Valve (Ø...
Page 26
IDU, user will not be able to record data. This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a “.CSV” file and emailed to an LG representative to assist with diagnostic evaluations. Recommended Minimum PC Configuration: •...
PERFORMANCE DATA “Cooling Capacity” on page 28 “Heating Capacity” on page 30 “Maximum Heating Capacity” on page 32 “Air Flow and Temperature Distributions Graphs” on page 34...
EQUIPMENT SELECTION PROCEDURE Cooling/Heating Correction Factors For Single Zone Art Cool Mirror systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, de- termine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction factors as shown in Figures 5 through 8.
LG Electronics, U.S.A., Inc., In all cases, the designer, installer, and contractor should understand if the suggested method is used, it is used at their own risk. LG Electronics U.S.A., Inc., takes no responsibility and offers no warranty, expressed or implied, in law or in fact, including •...
Page 40
BUILDING VENTILATION DESIGN GUIDE Method 2: Unconditioned Outdoor Air (Non-Ducted, Natural Ventilation) Natural ventilation devices, such as operable windows or louvers may be used to ventilate the building when local code permits. The open area of a window or the free area of a louver must meet the minimum percentage of the net occupied floor area (Figure 10). Advantages Disadvantages •...
PLACEMENT CONSIDERATIONS Selecting the Best Location DANGER cause serious bodily injury or death. Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it. Do not install the unit in a location where acidic solution and spray (sulfur) are often used as this may cause serious bodily injury or death. Do not use the unit in environments where oil, steam, or sulfuric gas are present as this may cause serious bodily injury or death.
Page 42
PLACEMENT CONSIDERATIONS Indoor Unit Clearance/Outdoor Unit Installation Figure 12: Single Zone Indoor Unit Clearance Requirements. Indoor Unit Best Location More than 4 inches Minimum clearance Follow recommended best practices when choosing an indoor location for the single zone indoor unit. from ceiling - “A”...
Page 43
PLACEMENT CONSIDERATIONS Outdoor Unit Clearances Minimum Clearance Requirements for Single-Zone Art Cool Mirror Systems Proper clearance for the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet and outlet and minimum allowable space requirements as illustrated in the diagrams below. Specific clearance requirements in the diagram below are for the single-zone Art Cool Mirror wall mount systems.
Outdoor unit pipe system. Refer to Figure 15 for maximum length and elevation of piping. Outdoor unit Indoor unit Table 21: Single-Zone Art Cool Mirror Wall-Mount Refrigerant Piping System Limitations. LA090HSV4 LA120HSV4 LA180HSV4 LA240HSV3 Longest total equivalent piping length 65.6 feet 65.6 feet...
INSTALLATION & LAYOUT BEST PRACTICES Refrigerant Piping System Layout Figure 17: Installing Piping Above and Below an Obstacle. Obstacles When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant pipe run, it is best practice to route the pipe over the obstacle.
Page 48
Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve.
INSTALLATION & LAYOUT BEST PRACTICES Piping Connections Single Zone Art Cool Mirror Outdoor Unit Connections 1. Remove the tubing cover from the unit by loosening the fastening screws (Figures 23 and 24). 2. Align the center of the refrigerant pipe and corresponding connection as shown in Figures 26 and 27. 3.
Page 50
INSTALLATION & LAYOUT BEST PRACTICES Piping Connections Installation of Refrigerant Piping / Brazing Practices It is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust during installation. All joints are brazed in the field. Single Zone Art Cool Mirror refrigeration system Figure 28: Refrigerant Pipe Brazing.
ELECTRICAL CONNECTIONS Figure 29: LSU090HSV4/LSU120HSV4 Figure 30: LSU180HSV4/LAU240HSV3 Outdoor Electrical Outdoor Unit Electrical Connection. Outdoor Unit Electrical Connection. Connection 1. Remove the control cover from the unit by loosen- 1(L1) 2(L2) 1(L1) 2(L2) 3 ing the fastening screw (Figures 29 and 30). Terminal Block 2.
General Electrical strainer, check valves, oil separator, accu- LG Single Zone Art Cool Mirror systems are These units are available in 208-230V, 60 mulator, four-way reversing valve, electronic comprised of a single outdoor unit connected Hz, 1-phase power supply.
ACRONYMS Table 29: Table of Acronyms. Acrylonitrile Butadiene Styrene Indoor Unit Air Conditioner International Organization for Standardization Advanced Control Platform Kilo Watts American Society of Heating, Refrigeration, and ASHRAE Light Emitting Diode Air Conditioning American Wire Gauge Thousands BTUs per hour BLDC Brushless Digitally Controlled/Direct Maximum Circuit Ampacity...
Page 55
20001747 ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics Commercial Products Support 1-888-865-3026 USA Follow the prompts for commercial A/C products. LG Electronics, U.S.A., Inc. Commercial Air Conditioning Division EM_SZ_ArtCoolMirror_HSV4_HSV3_12_15 4300 North Point Parkway Supersedes: EM-SZ-ArtCoolMirror-HSV4-3-15 Alpharetta, Georgia 30022 DFS-EM-AA-001-US_014B06...